2007-02-09 17:40:32BUILDING PLAN REVIEW
 PERMIT:06071011
 ADD:2505METROCENTRE BLVD
 CONT:PATE CHERNIN & ASSO. INC.
 TEL: (561)792-2757
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)OK
  
 2)OK
  
 3)OKHOWEVER, ELEVATION #6 ON SHEET A-4 DOES NOT
 SHOW THE DEPT OF THE SINK OR ANY PIPES BELOW THE SINK.
 SHOW HOW THE REQUIREMENTS OF FBC.11-4.24 WILL BE MET.
  
 4)THE LEGENDNEEDS TO BE MORE SPECIFIC WITH THE
 SYMBOLS FOR THE EXISTING AND NEW PARTITIONS. THE SYMBOL
 IS THE SAME FOR EACH WALL. WALL TYPES I AND 2 SHOULD BE
 DIFFERENT HOWEVER, ON THE DRAWINGS THE NUMBERS ARE THE
 SAME FOR BOTH TYPE OF WALLS. CLARIFY.
 HOW CAN DIFFERENT SYMBOLS REPRESENT THE SAME SIZE AND
 TYPE OF WALLS? SEE SHEET A-1.
  
 5) THE ELEVATION DETAIL #9 ON SHEET A-3 DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A-1. WHERE IS THE
 SECOND DOOR? ALSO SEE ELEVATION DETAIL #4 ON SHEET A-3.
 ALL DETAILS SHALL CORRESPON WITH THE FLOOR PLAN.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726