| Plan Review Notes For Permit 06071011 |
| Permit Number |
06071011 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-02-09 17:40:32 | BUILDING PLAN REVIEW | | | PERMIT:06071011 | | | ADD:2505METROCENTRE BLVD | | | CONT:PATE CHERNIN & ASSO. INC. | | | TEL: (561)792-2757 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 3RD | | | ACTION: DENIED | | | | | | 1)OK | | | | | | 2)OK | | | | | | 3)OKHOWEVER, ELEVATION #6 ON SHEET A-4 DOES NOT | | | SHOW THE DEPT OF THE SINK OR ANY PIPES BELOW THE SINK. | | | SHOW HOW THE REQUIREMENTS OF FBC.11-4.24 WILL BE MET. | | | | | | 4)THE LEGENDNEEDS TO BE MORE SPECIFIC WITH THE | | | SYMBOLS FOR THE EXISTING AND NEW PARTITIONS. THE SYMBOL | | | IS THE SAME FOR EACH WALL. WALL TYPES I AND 2 SHOULD BE | | | DIFFERENT HOWEVER, ON THE DRAWINGS THE NUMBERS ARE THE | | | SAME FOR BOTH TYPE OF WALLS. CLARIFY. | | | HOW CAN DIFFERENT SYMBOLS REPRESENT THE SAME SIZE AND | | | TYPE OF WALLS? SEE SHEET A-1. | | | | | | 5) THE ELEVATION DETAIL #9 ON SHEET A-3 DOES NOT | | | REFLECT THE FLOOR PLAN ON SHEET A-1. WHERE IS THE | | | SECOND DOOR? ALSO SEE ELEVATION DETAIL #4 ON SHEET A-3. | | | ALL DETAILS SHALL CORRESPON WITH THE FLOOR PLAN. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|