| Date |
Text |
| 2006-12-23 15:29:28 | *UNSAT 2ND REVIEW * |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| | STILL NEEDS TO BE ADDRESSED. PLEASE ALSO NEW NOTES |
| | BASED ON CHANGES AND/OR PLANS SUBMITTED. |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER WITH A NO |
| | OR OK. PLEASE SEE SOME MAY CONTAIN BOTH NO/OK, WHICH |
| | MEANS PART OF NOTE MAY HAVE BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: NO, PLEASE SEE NOT ALL AREAS CONTAIN THE |
| | REQUIRED CONTROLS FOR THE OCCUPANCY SENSOR DEVICES AS |
| | REQUIRED. PLEASE SEE NO MAXIMUM OVER RIDE/OC SENSOR |
| | TIMES ARE INDICATED. |
| | PLEASE SEE ENERGY CALCULATIONS INDICATE METHOD "A". |
| | PLEASE SEE 13-415.1.AB.1, PLEASE CLARIFY HOW METHOD "A" |
| | CAN BE USED FOR BUILD OUT OF AN EXISTING SPACE. PLEASE |
| | SEE THESE ALSO INDICATE MANUAL CONTROL FOR LIGHTING |
| | WHERE AUTO SHUT OFF IS BEING INSTALLED. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE |
| | LEVELS TO BE SPECIFIED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13. 13-415.1.ABC.1.1,.1.2,.1.3 |
| | ETC |
| | |
| | ** NEW NOTE (S) ** |
| | |
| | 1) NOTE: PLEASE STATE THE MINIMUM REQUIRED LEVELS FOR |
| | HORN AND STROBE DEVICES. PLEASE SEE FBC 11-4.28.1, .2, |
| | .3(4). |
| | THIS IS A NEW COMMENT. |
| | |
| | 2) NOTE: PLEASE SEE THAT PLANS STATE THE FOLLOWING |
| | CODES AT A MINIMUM 2002 NFPA-70, 2002 NFPA-72 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |