| 2007-01-03 16:13:23 | BUILDING PLAN REVIEW |
| | PERMIT:06071011 |
| | ADD:2505METROCENTRE BLVD |
| | CONT:PATE CHERNIN & ASSO. INC. |
| | TEL: (561)792-2757 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND. |
| | ACTION: DENIED |
| | |
| | 1) 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 2) THE EXTERIOR AREA OF THE RECEPTION COUNTER SHALL |
| | MEET ONE OF THE REQUIREMENTS OF 11-7.2. WHERE A PORTION |
| | OF THE MAIN COUNTER SHALL BE A MINIMUM OF 36 INCHES IN |
| | LENGTH AND A MAXIMUM HEIGHT OF 36 INCHES. |
| | |
| | 3)11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK (SEE FIGURE 11-32 |
| | ).SHOW ON THE DRAWINGS HOW REQUIREMENTS OF |
| | SEC.11-4.24 WILL BE MET. SHEET A-1 ROOM #003. |
| | |
| | 4)THE LEGENDNEEDS TO BE MORE SPECIFIC WITH THE |
| | SYMBOLS FOR THE EXISTING AND NEW PARTITIONS. THE SYMBOL |
| | IS THE SAME FOR EACH WALL. WALL TYPES I AND 2 SHOULD BE |
| | DIFFERENT HOWEVER, ON THE DRAWINGS THE NUMBERS ARE THE |
| | SAME FOR BOTH TYPE OF WALLS. CLARIFY. |
| | |
| | 5) THE ELEVATION DETAIL #9 ON SHEET A-3 DOES NOT |
| | REFLECT THE FLOOR PLAN ON SHEET A-1. WHERE IS THE |
| | SECOND DOOR? ALSO SEE ELEVATION DETAIL #4 ON SHEET A-3. |
| | ALL DETAILS SHALL CORRESPON WITH THE FLOOR PLAN. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |