2006-08-04 00:00:00*** DENIED ***
 1) RETURN AIR TRANSFER DUCTS FROM D.C.
 OFFICE #007 TO WAR ROOM #005 NEEDS TO BE
 SIZED.
  
 2) ARE DOORS TO MECHANICAL ROOM
 LOUVERED? PLEASE SHOW ON PLANS (IF NOT
 PROVIDE RETURN AIR TO AHU).
  
 3) PROVIDE PRODUCT APPROVAL FOR A/C
 CONDENSER STAND.
  
 4) PLEASE SEE ENERGY CALCULATIONS FRONT
 PAGE, MAX TONNAGE 5.0, TWO A/C SYSTEMS
 ARE BEING INSTALLED A 5 TON AND A 4 TON
 WOULD MAKE MAX TONNAGE 9 TONS.
  