| Plan Review Notes For Permit 06071011 |
| Permit Number |
06071011 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-04 00:00:00 | *** DENIED *** | | | 1) RETURN AIR TRANSFER DUCTS FROM D.C. | | | OFFICE #007 TO WAR ROOM #005 NEEDS TO BE | | | SIZED. | | | | | | 2) ARE DOORS TO MECHANICAL ROOM | | | LOUVERED? PLEASE SHOW ON PLANS (IF NOT | | | PROVIDE RETURN AIR TO AHU). | | | | | | 3) PROVIDE PRODUCT APPROVAL FOR A/C | | | CONDENSER STAND. | | | | | | 4) PLEASE SEE ENERGY CALCULATIONS FRONT | | | PAGE, MAX TONNAGE 5.0, TWO A/C SYSTEMS | | | ARE BEING INSTALLED A 5 TON AND A 4 TON | | | WOULD MAKE MAX TONNAGE 9 TONS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|