| Notes |
| Date |
Text |
| 2006-08-04 00:00:00 | *** UNSAT ** | | | | | | ** PLEASE KNOW, PLANS WEREONLY | | | SUBMITTED FOR "PLANREVIEW" AND HAS NOT | | | BEEN SUBMITTED FOR PERMIT. | | | | | | 1) NOTE: PLEASE CLARIFY THE GFI RECEPT | | | FOR CU'S. | | | 210.63,210.8 | | | | | | 2) NOTE: PLEASE CLARIFY THE MEANS OF | | | DISCONNECT FOR THE AHU'S. | | | 440.11. | | | | | | 3) NOTE: PLEASE SEE FBC CHAPTER CHAPTER | | | 13. | | | 13-415.1.ABC.1.1,.1.2,.1.3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|