Plan Review Notes
Plan Review Notes For Permit 06071011
Permit Number 06071011
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-04 00:00:00*** UNSAT **
  
 ** PLEASE KNOW, PLANS WEREONLY
 SUBMITTED FOR "PLANREVIEW" AND HAS NOT
 BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE CLARIFY THE GFI RECEPT
 FOR CU'S.
 210.63,210.8
  
 2) NOTE: PLEASE CLARIFY THE MEANS OF
 DISCONNECT FOR THE AHU'S.
 440.11.
  
 3) NOTE: PLEASE SEE FBC CHAPTER CHAPTER
 13.
 13-415.1.ABC.1.1,.1.2,.1.3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH