Plan Review Notes
Plan Review Notes For Permit 06071011
Permit Number 06071011
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-04 00:00:00 
  
 DENIED
  
 1) REMOVE ALL REFERENCES TO THE 2001
 FBC. DRAWINGS AND SPECIFICATIONS SHALL
 COMPLY WITH THE 2004 FBC WITH
 AMMENDMENTS. ALSO THE GENERAL CODE
 ANALYSIS ON A-2 USES 2001 SECTIONS AND
 TABLES PLEASE CORRECT
  
 2) SPECIFY SAFTY GLAZING FOR GLASS IN
 WALL BETWEEN RECEPTION AND CONFRENCE
 ROOM PER 2406.3 FBC
  
 3) DOOR SCHEDULE HAS DOOR #3 AS 2'-0"
 MAY BE A MISPRINT?
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW