| 2006-12-19 11:58:54 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE NO OCP IS BEING SHOWN ON RISER FROM |
| | GENERATOR TO ATS AND EXISTING EQUIPMENT. |
| | PLEASE SEE 445.13 FOR SIZING OF THE CONDUCTORS. |
| | |
| | 2) NOTE: PLEASE SEE LETTER IS PACKAGE FROM THE |
| | ELECTRICAL CONTRACTOR MENTIONS CONSIDERATION FOR NEC |
| | 250.20A IS BEING TAKEN WHICH IS A SECTION FOR |
| | SEPARATELY DERIVED SYSTEMS. PLEASE SEE IF THIS GOING TO |
| | BE A SD SYSTEM, THEN THE RISER WOULD NEED TO SHOW THE |
| | GROUNDING AT THE GENERATOR ACCORDING TO 250.50. |
| | PLEASE ALSO INDICATE OF THE EXISTING ATS IS A 4-POLE |
| | UNIT. |
| | PLEASE INDICATE THE VOLTAGE ON THE PLANS/RISER AS WELL |
| | AS THE SPECS SHEETS SUBMITTED. |
| | |
| | ** A CALL WAS PLACED TO THE ELECTRICAL CONTRACTOR ON |
| | 12/19/07 AT 10:23AM. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |