| Permit Number |
06070994 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-12-26 11:49:50 | PERMIT: 06070994 | | | ADD: 300 EXECUTIVE CENTER DR. | | | CONT: CLINLOR ELECTRIC | | | TEL: (386)774-1020 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) COMPLIED. | | | | | | 3) COMPLIED. | | | | | | 4) COMPLIED. | | | | | | 5) COMPLIED. | | | | | | 6) COMPLIED. | | | | | | 7) COMPLIED. | | | | | | 8)3RD REQUEST FOR THE TYPE OF FASTENER TO BE | | | USED TO FASTEN THE GENERATOR FRAME TO THE | | | EXISTING CONCRETE DECK. GENERATOR SLAB & | | | ANCHOR REQUIREMENT | | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | | PLUS PROVIDE PLANS WITH THE INFORMATION | | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | | THE DEVICE REQUIRES WITHOUT LOAD | | | REDUCTION. | | | 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND | | | SLIDING | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|