Plan Review Notes
Plan Review Notes For Permit 06070994
Permit Number 06070994
Review Stop B
Sequence Number 3
Notes
Date Text
2006-12-26 11:49:50PERMIT: 06070994
 ADD: 300 EXECUTIVE CENTER DR.
 CONT: CLINLOR ELECTRIC
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8)3RD REQUEST FOR THE TYPE OF FASTENER TO BE
 USED TO FASTEN THE GENERATOR FRAME TO THE
 EXISTING CONCRETE DECK. GENERATOR SLAB &
 ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDING
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026