| 2006-08-09 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06070994 |
| | ADD: 300 EXECUTIVE CENTER DR. |
| | CONT: CLINLOR ELECTRIC |
| | TEL: (386)774-1020 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLEASE PROVIDE DOCUMENTS FOR SIZE OF |
| | GENERATOR AND ALSO FOR THE SIZE OF FUEL |
| | TANK TO ACCOMPANY THE GENERATOR. |
| | |
| | 3) VALUE IS LOW WILL ASSESS VALUE FROM |
| | MARSHALL & SWIFT IF VALUE IS NOT |
| | CORRECTED. |
| | |
| | 4) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 5) PLANS INDICATE THEY ARE THE PROPERTY |
| | (DRAWN BY) DONNELLY ENGINEERING, |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 6) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G) FLOOD ZONE |
| | |
| | 7) SITE PLAN ILLEGIBLE. |
| | 106.1.2 ADDITIONAL DATA. THE |
| | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, |
| | STRESS DIAGRAMS, AND OTHER |
| | DATA NECESSARY TO DESCRIBE THE |
| | CONSTRUCTION OR INSTALLATION AND THE |
| | BASIS OF CALCULATION. ALL DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | REQUIRED BY THE BUILDING OFFICIAL TO BE |
| | PREPARED BY AN ARCHITECT OR ENGINEER |
| | SHALL BE AFFIXED WITH THIER OFFICIAL |
| | SEAL, SIGNATURE AND DATE AS STATE LAW |
| | REQUIRES. |
| | |
| | 8) GENERATOR SLAB & ANCHOR REQUIREMENT |
| | PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| | PLUS PROVIDE PLANS WITH THE INFORMATION |
| | DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE |
| | THE DEVICE REQUIRES WITHOUT LOAD |
| | REDUCTION. |
| | SECOND, PROVIDE INFORMATION ON THE |
| | SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| | WIREMESH, FIBER MESH OR IF STEEL REBAR |
| | WILL BEUSED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |