Plan Review Notes
Plan Review Notes For Permit 06070992
Permit Number 06070992
Review Stop E
Sequence Number 5
Notes
Date Text
2007-07-16 17:38:51**** UNSAT ****
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES TWO
 SMALL APPLIANCE CIRCUITS ALONG WITH DINING ROOM AND
 EACH AT 1500VA YET THE LOAD CALCULATIONS DO NOT
 CORRELATE WITH THIS.
 PLEASE SEE 210.52B1, 210.11C1, AND 220.16
  
 2) NOTE: PLEASE SEE AS PLANS ARE COMING BACK FOR
 CORRECTIONS; PLEASE CORRECT THE DESIGNATION OF THE
 SMOKE DETECTION DEVICES AS THESE APPEAR TO BE SMOKE
 ALARMS AND NOT SMOKE DETECTORS PER NFPA-72
 DEFINITIONS.
 PLEASE SEE BOTH SMOKE DEVICES ARE SHOWN INSIDE THE
 BEDROOM/SLEEPING ROOM. PLEASE SEE NFPA-72 11.5.1.1.1
 WHICH REQUIRES THESE INSIDE AND OUTSIDE ROOM.
  
 3) NOTE: PLEASE CLARIFY THE *EXISTING* BATH GFI CIRCUIT
 WITH 1500AV LOAD?
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  