| Notes |
| Date |
Text |
| 2007-07-16 17:38:51 | **** UNSAT **** | | | | | | 1) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES TWO | | | SMALL APPLIANCE CIRCUITS ALONG WITH DINING ROOM AND | | | EACH AT 1500VA YET THE LOAD CALCULATIONS DO NOT | | | CORRELATE WITH THIS. | | | PLEASE SEE 210.52B1, 210.11C1, AND 220.16 | | | | | | 2) NOTE: PLEASE SEE AS PLANS ARE COMING BACK FOR | | | CORRECTIONS; PLEASE CORRECT THE DESIGNATION OF THE | | | SMOKE DETECTION DEVICES AS THESE APPEAR TO BE SMOKE | | | ALARMS AND NOT SMOKE DETECTORS PER NFPA-72 | | | DEFINITIONS. | | | PLEASE SEE BOTH SMOKE DEVICES ARE SHOWN INSIDE THE | | | BEDROOM/SLEEPING ROOM. PLEASE SEE NFPA-72 11.5.1.1.1 | | | WHICH REQUIRES THESE INSIDE AND OUTSIDE ROOM. | | | | | | 3) NOTE: PLEASE CLARIFY THE *EXISTING* BATH GFI CIRCUIT | | | WITH 1500AV LOAD? | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|