| Plan Review Notes For Permit 06070991 |
| Permit Number |
06070991 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-07-16 18:17:46 | | | | | | | **** UNSAT **** | | | | | | 1) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES FOUR | | | SMALL APPLIANCE CIRCUITS ALONG WITH DINING ROOM AND | | | EACH AT 1500VA YET THE LOAD CALCULATIONS DO NOT | | | CORRELATE WITH THIS. ONLY SHOWS TWO TOTAL. | | | PLEASE SEE 210.52B1, 210.11C1, AND 220.16 | | | | | | 2) NOTE: PLEASE SEE AS PLANS ARE COMING BACK FOR | | | CORRECTIONS; PLEASE CORRECT THE DESIGNATION OF THE | | | SMOKE DETECTION DEVICES AS THESE APPEAR TO BE SMOKE | | | ALARMS AND NOT SMOKE DETECTORS PER NFPA-72 | | | DEFINITIONS. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|