Plan Review Notes
Plan Review Notes For Permit 06070950
Permit Number 06070950
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-20 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE CLARIFY FEEDERS INTO
 EXISTING PANEL.
 PLEASE SEE RISER SHOWS 150A FEED TO THE
 NEW 100 MLO?
 240.4,240.21,310.16,215.5,
  
 2) NOTE: PLEASE SEE MISSING AIC RATING
 FOR NEW MAINS/ SERVICE EQUIPMENT.
 110.9/
  
 3) NOTE: PLEASE VERIFY AND SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANEL.
 250.110, 250.122,250.24B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  