| 2006-08-07 00:00:00 | REVIEW IN PROGRESS |
| | **** UNSAT **** |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. PLEASE KNOW |
| | ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | ** THIS COMMENT IS NOT FOR KAMM |
| | CONSULTING ENGINEER'S. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE TO UPDATE CODES |
| | TO THE FOLLOWING AT THIS TIME FOR THIS |
| | PROJECT. |
| | 2002 NFPA-70, 2002 NFPA-72 AND 2003 |
| | NFPA-101. |
| | |
| | 2) NOTE: PLEASE PLACE ROOM AND AREA |
| | DESIGNATIONS ON PLANS. |
| | PLEASE CLARIFY IF THERE ARE ANY "IT: |
| | ROOMS. IF SO, PLEASE SEE NFPA-75 AND NEC |
| | 645 FOR REQUIRED ELECTRICAL SHUT DOWN, |
| | RATING OF ROOM ETC. |
| | |
| | 3) NOTE: PLEASE SEE NOTE #5 ON KEY NOTES |
| | ON E2.1, MENTIONS TO "SEE SCHEDULE NOT |
| | ON THIS SHEET". PLEASE VERIFY WHICH |
| | SHEET AND OR WHERE TO VERIFY. |
| | |
| | 4) NOTE: PLEASE KNOW, PER THE NOTE ABOVE |
| | PLEASE BE SURE ALL OCC SENSR TYPE |
| | DEVICES ARE NOTE W/ MAX TIMES. ( OCC |
| | TYPE 30,MINS) AND TIMED 0-4 HRS.) |
| | FBC CHPATER 13, 13-415.1.ABC.1.1, .1.2, |
| | AND .1.3 |
| | |
| | 5) NOTE: PLEASE VERIFY THAT PANEL "C" IS |
| | BEING SHOWN AS MLO. PLEASE SEE 240.21, |
| | AS TAPPED CONDUCTORS SHALL TERMINATE IN |
| | OCP WHICH LIMITS THE LOADS. PLEASE ALSO |
| | SEE 408.16 WHICH ALSO REQUIRES A MEANS |
| | OF OCP. |
| | ** PLEASE KNOW, IF ONE IS NOT FOUND, ONE |
| | WILL BE REQUIRED OT BE INSTALLED. |
| | |
| | 6) NOTE: PLEASE HAVE THE ENGINEER OF |
| | RECORD SIGN WITH SIGNATURE AS RECOGNIZED |
| | BY THIS OFFICE AND AS PREVIOUSLY ON |
| | FILE. |
| | FS 471.025, FAC 61G15-23.002 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| 2006-08-06 00:00:00 | IN ELEC FOR REIVEW. |