| 2006-09-17 00:00:00 | **** UNSAT 2ND REVIEW.*** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND NEW NOTE. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW WITH NEW |
| | NOTE ADDED AT THE BOTTOM. |
| | |
| | ********** UNSAT ************* |
| | |
| | 1) NOTE: NO/OK, RISER MENTIONS THE METER |
| | MAIN FEEDS TWO MLO'S, YET THE 2ND RISER |
| | FOR INSIDE EQUIPMENT SHOWS TWO MCB'S? |
| | PLEASE CORRELATE. CALCULATIONS OK, |
| | HOEVER SEE NEW NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE LABEL ALL PANELS AND |
| | DISCONNECT ON PLANS. PLEASE CLARIFY |
| | WHICH PANEL IS BEING FED WITH THE |
| | GENERATOR AND PLEASE SUBMIT LOAD |
| | CALCUALTIONS FOR THAT PANEL AND ALL |
| | LOADS. PLEASE KNOW, ANY HEAT STRIPS IN |
| | AHU'S SHALL BE FIGURED AT 100% UNLESS |
| | LOADING SHEDDING IS PROVIDED. PLEASE |
| | PROVIDE DETAIL IF THIS IS THE CASE. |
| | PLEASE SEE LOADS AS SHOWN EXCEED RATING |
| | OF THE GENERATOR. |
| | PLEASE SEE NO PANEL SCHEDULES ARE |
| | PROVIDED SHOWING THE NEW OCP ETC FOR NEW |
| | EM SUB PANEL.?? |
| | 220,702.5, 240.4,310.16,215.5 ETC |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK, SHOWN WITH 5' MIN ON ALL |
| | SIDES. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: NO, THIS IS THE SAME. ALL |
| | SHEETS DONE BY THE CONTRACTOR. (NOT |
| | MANUFACTURES) |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE KNOW ALL PLANS/DESIGNS |
| | SHALL CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | SAID PLANS/DESIGN AND LOAD CALCULATIONS. |
| | |
| | |
| | *** NEW NOTE *** |
| | |
| | 8) NOTE: PLEASE SUBMIT TWO COMPLETE SETS |
| | MADE INTO SETS. PLEASE SEE LOOSE SHEETS |
| | SUBMITTED AND PLEASE SEE ONLY ONE COPY |
| | OF THE PANEL SCHEDULES/LOAD |
| | CALCULATIONS, ONE COPY OF OTHER SHEETS |
| | AS WELL. |
| | MUST HAVE TWO SETS MIN. |
| | FBC 106.1, 106.1.2 ADMIN SECT. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |