| Date |
Text |
| 2006-07-27 00:00:00 | ********** UNSAT ************* |
| | |
| | 1) NOTE: PLEASE LABEL ALL PANELS AND |
| | DISCONNECT ON PLANS. PLEASE CLARIFY |
| | WHICH PANEL IS BEING FED WITH THE |
| | GENERATOR AND PLEASE SUBMIT LOAD |
| | CALCUALTIONS FOR THAT PANEL AND ALL |
| | LOADS. PLEASE KNOW, ANY HEAT STRIPS IN |
| | AHU'S SHALL BE FIGURED AT 100% UNLESS |
| | LOADING SHEDDING IS PROVIDED. PLEASE |
| | PROVIDE DETAIL IF THIS IS THE CASE. |
| | PLEASE SEE LOADS AS SHOWN EXCEED RATING |
| | OF THE GENERATOR. |
| | PLEASE SEE NO PANEL SCHEDULES ARE |
| | PROVIDED SHOWING THE NEW OCP ETC FOR NEW |
| | EM SUB PANEL.?? |
| | 220,702.5, 240.4,310.16,215.5 ETC |
| | |
| | 2) NOTE: PLEASE SEE FEEDERS FROM MAIN IS |
| | NOT LARGE ENOUGH. PLEASE SEE |
| | 310.16,240.4 FOR MIN SIZES. SHOWS #1 ON |
| | 200A'S?? |
| | |
| | 3) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS. |
| | 250.24B,250.110,250.122 ETC |
| | |
| | 4) NOTE: PLEASE SEE RISER SHOWS A SE |
| | RATED ATS AND SPECS SUBMITTED DO NOT |
| | CORRELATE. |
| | 110.3,90.7 |
| | |
| | 5) NOTE: PLEASE PROVIDE ALL MINIMUM |
| | CLEARENCES FOR GEN. PLEASE PROVIDE MIN |
| | CLEARENCES RECOMMENDED BY MANUFACTURE. |
| | PLEASE KNOW, THIS OFFICE HAS OBTAINED |
| | LTRS WHICH REQUIRES A MIN OF 5' FROM ALL |
| | SURROUNDING FOR THIS TYPE OF UNIT. |
| | 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE MISSING |
| | DISCONNECTING MEANS FOR FEEDERS FROM GEN |
| | AT HOUSE. 225.31-225.39. |
| | THE DISCONNECTSHALL NOT REQUIRE OCP, |
| | HOWEVER MUST BE GROUPED WITHEXISTING |
| | MAINS AND RATED FOR THE LOAD SERVED. |
| | ** BRKR ON GEN IS NOT ACCEPTABLE. |
| | |
| | 7) NOTE: PLEASE KNOW ALL PLANS/DESIGNS |
| | SHALL CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | SAID PLANS/DESIGN AND LOAD CALCULATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |