Plan Review Notes
Plan Review Notes For Permit 06070941
Permit Number 06070941
Review Stop B
Sequence Number 4
Notes
Date Text
2007-01-23 11:31:24BUILDING PLAN REVIEW
 PERMIT: 06070941
 ADD: 1711 LONGWOOD DR
 CONT: SOUTH EAST GENERAL CONT.
 TEL: (561460-9697
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4A) SEMI -COMPLIED, THE NUCAR BUILDING PLANS NOW HAVE
 THE RIGHT
 MUNICIPALITY BUT BOTH SETS OF SEALED PLANS, THE
 SIGNATURE IS A COPY
 OR RUBBER STAMP SIGNATURE OF COREY D. NORRIS P. E.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGNPROFESSIONAL
 AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4B) THE STRUCTURAL DESIGN CALCULATIONS FOR THE NUCOR
 BUILDING
 SYSTEM BY JEFFERY P. BARKMAN, P. E. ONE SET HAS THE
 ORIGINAL SIGNATURE AND SEAL,
 THE OTHER SET THE SIGNATURE IS COPIED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) PRODUCT APPROVALS:
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING DOORS - NOT REVIEWED BY THE DESIGNER OF
 RECORD
 B) OVERHEAD GARAGE DOORS- NOT A FLORIDA APPROVAL OR
 MIAMI-DADE REPORT.
 WILL REQUIRE ORIGINAL REPORT WITH ENGINEERS
 SIGNATURE AND SEAL, A THIRD PARTY
 QUALITY ASSURANCE PARTY APPROVED BY THE STATE.
 C) ROOFING ASSEMBLIES, NOT REVIEWED BY THE DESIGNER OF
 RECORD, ALSO THE STRESS ON THE PANELS WAS
 NOT
 HIGHLIGHTED AS REQUESTED IN THE MEETING WITH THE
 DESIGNER AND CONTRACTOR.
  
 10)THIRD REQUEST, W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11)3RD REQUEST, OVERHEAD DOOR,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12)COMPLIED.
  
 13) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  