Plan Review Notes
Plan Review Notes For Permit 06070941
Permit Number 06070941
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-10-25 08:18:051. PLANS DO NOT DECLARE TYPE OF STORAGE ANTICPATED. 2.
 PLANS OR INFORMATION PROVIDED DOES NOT INDICATE IF THE
 EXISTING BUILDING IS FIRE SPRINKLER PROTECTED. 3.
 PLEASE ILLUSTRATE EXIT DOOR LOCATIONS FOR THE EXISTING
 BUILDING.
 4. NO PORTABLE FIRE EXTINGUISHERS SHOWN WITH DRAWINGS.
 5. NO DOOR SCHEDULE OR HARDWARE SCHEDULE.
 6. PLEASE DECLARE EXISTING BUILDING CONSTRUCTION TYPE
 AND OCCUPANCY CLASSIFICATION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709