Plan Review Notes
Plan Review Notes For Permit 06070941
Permit Number 06070941
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-15 16:47:46*** UNSAT2ND REVIEW ***
  
 PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND NEW
 NOTES.
  
 1) NOTE:NO, ONLY ONE SET OF ELECTRICLA PLANS
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT TWO COMPLETE SETS
 MINIMUM (UP TO THREE MAY BE SUBMITTED).
 PLEASE SEE ONLY ONE SET OF ELECTRICAL ,
 ONLY ONE SHEET A/2, AND FOUR A/1'S. ONLY
 ONE LARGE ZONING SITE/SURVEY PLANS.
 PLEASE BE SURE TO ATTACH ALL SHEETS INTO
 EACH SET IN A NEAT AND ORDERLY FASHION.
 MANY OF THE SHEETS ARE SEPARATED ETC.
 FBC 106.1
  
 2) NOTE: OK, HOWEVER SEE NOTE ABOVE AND SEE NEW NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE ALL SETS CONTAIN
 AN ORIGINAL SIGNATURE, DATE AND SEAL BY
 ALL ENGINEERS AND DESIGNERS OF RECORD.
 PLEASE SEE BUILDING REVIEW COMMENTS TO
 FOLLOW AS THE "NUCOR" SETS CONTAIN A
 RAISED SEAL OVER A "PHOTO-COPIED"
 SIGNATURE FROM THE DESIGN PROFESSIONSL.
 PLEASE SEE STRUCTURAL DESIGN CALCS WHERE
 ONLY ONE SET CONTAINS AN ORIGINAL
 SIGNATURE..
 FS 471.025, FAC 61G15-23.002.
  
 3) NOTE: NO, STILL UNCLEAR AS NEW FOOTING ECT ARE BEING
 SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE THE ELECTRICAL
 WITH BUILDING AS THE BUILDING IS NEW YET
 THE ELECTRICAL PLANS HAS NOTES THAT THIS
 IS ALL EXISTING.?
  
 4) NOTE: NO, PLEASE SEE VALUE HAS NOT YET BEEN ADJUST.
 PLEASE KNOW, ONE WILL BE ASSESSED USING MARSHALL'S &
 SWIFT GUIDE AS ADOPTED UNDER THE FBC IF NOT ADJUSTED
 FOR COMPLETE SCOPE FOR ALL .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE APPLIED VALUE SHALL
 BE BASED ON ALL LABOR AND MATERIALS,
 EVEN IF ANY MATERIALS ARE OWNER
 SUPPLIED. PLEASE KNOW, A VALUE MAY BE
 ASSESSED BY THIS OFFICE. FBC 108.3
  
 5) NOTE:NO, SAME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE FOLLOWING
 CURRENT CODES ARE REFLECTED ON PLANS.
 PLEASE REF: 2002 NFPA-70, 2003 NFPA-101,
  
 PLEASE ALSO LIST THE 2004 FBC.
  
 6) NOTE:OK, AS THIS WAS NOT APPLICABLE.
  
 ** NEW NOTE **
  
 7) NOTE: PLEASE SEE FS 471.003 AND FS 481.229 AS A
 DRAFTING FIRM MAY NOT PROVIDE SIGNED AND SEALED
 DOCUMENTSFORARCHITECTURAL SERVICES OR ENGINEERING
 SERVICE WHEN WORK IS REQUIRED TO BE DONE BY THIS
 TRADES. PLEASE KNOW, UNLESS "EMPLOYED" BY THE ENGINEERS
 OF RECORD AS SHOWN. PLEASE BE SURE ALL REQUIRED SCOPE
 OF WORK AS MENTIONED ABOVE IS DONE BY THE ENGINEERS.
 WITH THEIR TITLE BLOCKS. ETC
 PLEASE CONTACT EITHER THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'SOR THE FLORIDA BOARD OF ARCHITECT'S LEGAL
 COUNSEL IF THERE ARE ANY QUESTIONS.
 THIS WAS NOT NOTED ON PREVIOUS REVIEW AS THIS HAS TO
 THE ATTENTION OF THIS OFFICE FROM THE STATE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  