| Date |
Text |
| 2006-10-15 16:47:46 | *** UNSAT2ND REVIEW *** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND NEW |
| | NOTES. |
| | |
| | 1) NOTE:NO, ONLY ONE SET OF ELECTRICLA PLANS |
| | SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT TWO COMPLETE SETS |
| | MINIMUM (UP TO THREE MAY BE SUBMITTED). |
| | PLEASE SEE ONLY ONE SET OF ELECTRICAL , |
| | ONLY ONE SHEET A/2, AND FOUR A/1'S. ONLY |
| | ONE LARGE ZONING SITE/SURVEY PLANS. |
| | PLEASE BE SURE TO ATTACH ALL SHEETS INTO |
| | EACH SET IN A NEAT AND ORDERLY FASHION. |
| | MANY OF THE SHEETS ARE SEPARATED ETC. |
| | FBC 106.1 |
| | |
| | 2) NOTE: OK, HOWEVER SEE NOTE ABOVE AND SEE NEW NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE ALL SETS CONTAIN |
| | AN ORIGINAL SIGNATURE, DATE AND SEAL BY |
| | ALL ENGINEERS AND DESIGNERS OF RECORD. |
| | PLEASE SEE BUILDING REVIEW COMMENTS TO |
| | FOLLOW AS THE "NUCOR" SETS CONTAIN A |
| | RAISED SEAL OVER A "PHOTO-COPIED" |
| | SIGNATURE FROM THE DESIGN PROFESSIONSL. |
| | PLEASE SEE STRUCTURAL DESIGN CALCS WHERE |
| | ONLY ONE SET CONTAINS AN ORIGINAL |
| | SIGNATURE.. |
| | FS 471.025, FAC 61G15-23.002. |
| | |
| | 3) NOTE: NO, STILL UNCLEAR AS NEW FOOTING ECT ARE BEING |
| | SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE THE ELECTRICAL |
| | WITH BUILDING AS THE BUILDING IS NEW YET |
| | THE ELECTRICAL PLANS HAS NOTES THAT THIS |
| | IS ALL EXISTING.? |
| | |
| | 4) NOTE: NO, PLEASE SEE VALUE HAS NOT YET BEEN ADJUST. |
| | PLEASE KNOW, ONE WILL BE ASSESSED USING MARSHALL'S & |
| | SWIFT GUIDE AS ADOPTED UNDER THE FBC IF NOT ADJUSTED |
| | FOR COMPLETE SCOPE FOR ALL . |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE APPLIED VALUE SHALL |
| | BE BASED ON ALL LABOR AND MATERIALS, |
| | EVEN IF ANY MATERIALS ARE OWNER |
| | SUPPLIED. PLEASE KNOW, A VALUE MAY BE |
| | ASSESSED BY THIS OFFICE. FBC 108.3 |
| | |
| | 5) NOTE:NO, SAME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE THE FOLLOWING |
| | CURRENT CODES ARE REFLECTED ON PLANS. |
| | PLEASE REF: 2002 NFPA-70, 2003 NFPA-101, |
| | |
| | PLEASE ALSO LIST THE 2004 FBC. |
| | |
| | 6) NOTE:OK, AS THIS WAS NOT APPLICABLE. |
| | |
| | ** NEW NOTE ** |
| | |
| | 7) NOTE: PLEASE SEE FS 471.003 AND FS 481.229 AS A |
| | DRAFTING FIRM MAY NOT PROVIDE SIGNED AND SEALED |
| | DOCUMENTSFORARCHITECTURAL SERVICES OR ENGINEERING |
| | SERVICE WHEN WORK IS REQUIRED TO BE DONE BY THIS |
| | TRADES. PLEASE KNOW, UNLESS "EMPLOYED" BY THE ENGINEERS |
| | OF RECORD AS SHOWN. PLEASE BE SURE ALL REQUIRED SCOPE |
| | OF WORK AS MENTIONED ABOVE IS DONE BY THE ENGINEERS. |
| | WITH THEIR TITLE BLOCKS. ETC |
| | PLEASE CONTACT EITHER THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEER'SOR THE FLORIDA BOARD OF ARCHITECT'S LEGAL |
| | COUNSEL IF THERE ARE ANY QUESTIONS. |
| | THIS WAS NOT NOTED ON PREVIOUS REVIEW AS THIS HAS TO |
| | THE ATTENTION OF THIS OFFICE FROM THE STATE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |