Plan Review Notes
Plan Review Notes For Permit 06070941
Permit Number 06070941
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-09-14 00:00:00*****DENIED*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONDERS ACCESS TO SAID
 PROPERTY OR PROPERTIES IN THE VICINITY.
  
 3.) EXITS TO REMAIN CLEAR AND
 UNOBSTUCTED.
  
 4.) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.) COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE 2004, 2004 EDITION.
  
 6.) PLEASE INDICATE/DISPLAY/SHOW
 LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE PROTECTION SYSTEM. HOW
 WILL THEY BE AFFECTED BY THE SCOPE OF
 WORK?
  
 7.) IF THE FIRE ALARM AND/OR SPRINKLER
 SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE
 OF WORK, SEPARATE SHOP DRAWINGS/PLANS
 AND PERMIT IS REQUIRED.
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  
  
 8.)