| 2006-08-09 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06070941 |
| | ADD: 1711 LONGWOOD DR |
| | CONT: SOUTH EAST GENERAL CONT. |
| | TEL: (561460-9697 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | NOTE THE NOTICE OF COMMENCEMENT |
| | SUBMITTED IS FOR A STRUCTURE IN DELRAY. |
| | |
| | 3) 61G1-16.004FL. ADMIN. CODE.PLANS |
| | PREPARED BY A REGISTERED ARCHITECT SHALL |
| | INCLUDE A TITLE BLOCK WHICH MUST: |
| | - STATE THE FIRM NAME, ADDRESS AND |
| | TELEPHONE NUMBER |
| | - STATE THE FIRM LICENSE NUMBER |
| | - STATE PROJECT NAME OR IDENTIFICATION |
| | - STATE DATE PREPARED |
| | - INCLUDE AN ORIGINAL SIGNATURE AND |
| | DATED SEAL |
| | - INCLUDE THE PRINTED NAME OF THE |
| | ARCHITECT SEALING THE PLANS |
| | PLANS ARE COPIES OF A PROJECT THAT WAS |
| | LOCATED IN PALM BEACH GARDENS , PROJECT |
| | NAME DUNCAN, AQUA VAC. |
| | |
| | 4)NUCAR BUILDING PLANS ARE COPIES SO ARE |
| | THE SIGNATURES: |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 5) FBC 104.2.1ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN.PLEASE COMPLY. |
| | |
| | 6A) PROVIDE SURVEY THAT IS LEGIBLE. |
| | |
| | 6B) SHEET A/1 INDICATES THAT TWO |
| | BUILDINGS APPEAR TO BE TIED TOGETHER |
| | FORMING ONE LARGE STRUCTURE IS THIS |
| | CORRECT? |
| | 106.1.2 ADDITIONAL DATA. THE |
| | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, |
| | STRESS DIAGRAMS, AND OTHER |
| | DATA NECESSARY TO DESCRIBE THE |
| | CONSTRUCTION OR INSTALLATION AND THE |
| | BASIS OF CALCULATION. ALL DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | REQUIRED BY THE BUILDING OFFICIAL TO BE |
| | PREPARED BY AN ARCHITECT OR ENGINEER |
| | SHALL BE AFFIXED WITH THIER OFFICIAL |
| | SEAL, SIGNATURE AND DATE AS STATE LAW |
| | REQUIRES. |
| | |
| | 7) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G) SQ. FT. FOOTPRINT (TOTAL BUILDING) |
| | H) OCCUPANT LOAD |
| | I) FLOOD ZONE |
| | J) FLOOD ELEVATION |
| | K)L.O.M.R. |
| | |
| | 8) SHEET A/1 OF DIAZ DRAWINGS, |
| | CORRECTIONS: |
| | |
| | 8A) NOTE (2C) INDICATES PLANS ARE |
| | DESIGNED TO ASCE 7-98 SEE 1609 & CHAPTER |
| | 35 REFRENCED STANDARDS ASCE7-02. |
| | |
| | 8B) SOIL BEARING OF 2000PSF PLEASE |
| | PROVIDE SOILS REPORT. |
| | |
| | 8C) NOTE 14 INDICATES AN EXTERIOR PORCH |
| | STUCCO CEILING? PLEASE INDICATE WHERE |
| | THIS CAN BE LOCATED. |
| | |
| | 8D) NOTE 15 REFRENCES THE 2001 FBC AND |
| | PBC AMENDMENTS DELETE BOTH ONLY |
| | AMENDMENTS TO 2004 FBC ARE CHAPTER 1 |
| | WHICH ARE ADMINISTRATIVE AND TO THAT |
| | JURISDICTION ONLY. |
| | |
| | 8E) NOTE 16 AGAIN INDICATES PBC |
| | AMENDMENTS PLEASE DELETE TO COUNTY |
| | AMENDMENTS. |
| | |
| | 8F) A/1 SCOPE OF WORK INDICATES THAT |
| | THERE IS AN APPARENT STRUCTURE AND JUST |
| | REPAIR OF BUILDING. THE PERMIT |
| | APPLICATION INDICATES "REPLACE" BUILDING |
| | AND THERE IS A DEMO PERMIT FOR A METAL |
| | BUILDING? PLEASE CLARIFY,CORRECT. |
| | |
| | 9) PRODUCT APPROVALS: |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) SWING DOORS |
| | B) OVERHEAD GARAGE DOORS |
| | C) ROOFING ASSEMBLIES |
| | |
| | 10) W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 12) E-1 INDICATES STOCK ROOM WHAT TYPE |
| | OF INVENTORY SHALL BE STORED? 106.1.2* |
| | WPB ADMINISTRATIVE CODE.301.1. |
| | |
| | MORE COMMENTS MAY BE FORTH COMING WITH |
| | NEW AND OR ADDITIONAL INFORMATION ON |
| | FUTURE REVIEWS. |