| Date |
Text |
| 2007-05-15 08:51:11 | REVISION DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | NOTE: PLEASE BE AWARE THAT THIS IS A REVISION AND FEES |
| | ARE DUE ON THIS REVISION AND FEES WILL BE DUE ON THE |
| | RESUBMITTED REVISION AND THATFUTURE PLAN REVIEWS WILL |
| | NOT BE DONE UNTIL FEES ARE PAID: |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **OK** |
| | |
| | 2. **OK** |
| | |
| | 3. **OK** |
| | |
| | 4. **OK** |
| | |
| | THE FOLLOWING ARE NEW CORRECTIONS REQUIRED ON THE |
| | RESUBMITTED REVISION FOR GAS PLAN REVIEW TO MEET CODE |
| | COMPLIANCE: |
| | |
| | 5. THE RESUBMITTED DRAWINGS NEED TO BE SIGNED AND |
| | SEALED BY THE DESIGN PROFESSIONAL OF RECORD LARRY M. |
| | SMITH, P.E. # 45997 WITH A TITLE BLOCK FROM SMITH |
| | ENGINEERING CONSULTANTS, INC. STATE AUTH. # 8228 THAT |
| | INCLUDES THE ADDRESS AND PHONE NUMBER PER CHAPTER 471, |
| | FLORIDA STATUTES. |
| | |
| | 6. PLEASE CORRECT THE TOTAL DISTANCE ON THE |
| | RESUBMITTED REVISION AS 100'-6" AND DELETE THE TWO |
| | TOTAL DISTANCES OF 133' AND 138' ON THE RESUBMITTED |
| | REVISION. |
| | |
| | 7. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | NOTE: PLEASE INDICATE THESE VALVES ON THE RESUBMITTED |
| | REVISION. |
| | |
| | 8. PLEASE NOTE THAT THE SIZING 402.4(32) INDICATED ON |
| | THE REVISION IS WRONG BECAUSE IT IS FOR 2.0 PSI |
| | UNDILUTED PROPANE AND THIS GAS SYSTEM IS 2.0 PSI |
| | NATURAL GAS. THE CORRECT SIZING TABLES FOR THIS SYSTEM |
| | ARE 402.4(3) SCH 40, 402.4(17) CSST, AND 402.4(21) PE. |
| | ALSO PLEASE DELETE THE FOLLOWING "3/4" POLYETHYLENE |
| | PLASTIC PIPE LENGTH (FT) 100' MAX. CAPACITY 1,801,000 |
| | BTUH" BECAUSE IT IS ALSO FOR 2.0 PSI UNDILUTED PROPANE |
| | AND THIS SYSTEM IS 2.0 PSI NATURAL GAS. PLEASE CORRECT |
| | AND RESUBMIT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |