Plan Review Notes
Plan Review Notes For Permit 06070921
Permit Number 06070921
Review Stop G
Sequence Number 4
Notes
Date Text
2007-05-15 08:51:11REVISION DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 NOTE: PLEASE BE AWARE THAT THIS IS A REVISION AND FEES
 ARE DUE ON THIS REVISION AND FEES WILL BE DUE ON THE
 RESUBMITTED REVISION AND THATFUTURE PLAN REVIEWS WILL
 NOT BE DONE UNTIL FEES ARE PAID:
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3. **OK**
  
 4. **OK**
  
 THE FOLLOWING ARE NEW CORRECTIONS REQUIRED ON THE
 RESUBMITTED REVISION FOR GAS PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 5. THE RESUBMITTED DRAWINGS NEED TO BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD LARRY M.
 SMITH, P.E. # 45997 WITH A TITLE BLOCK FROM SMITH
 ENGINEERING CONSULTANTS, INC. STATE AUTH. # 8228 THAT
 INCLUDES THE ADDRESS AND PHONE NUMBER PER CHAPTER 471,
 FLORIDA STATUTES.
  
 6. PLEASE CORRECT THE TOTAL DISTANCE ON THE
 RESUBMITTED REVISION AS 100'-6" AND DELETE THE TWO
 TOTAL DISTANCES OF 133' AND 138' ON THE RESUBMITTED
 REVISION.
  
 7. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 NOTE: PLEASE INDICATE THESE VALVES ON THE RESUBMITTED
 REVISION.
  
 8. PLEASE NOTE THAT THE SIZING 402.4(32) INDICATED ON
 THE REVISION IS WRONG BECAUSE IT IS FOR 2.0 PSI
 UNDILUTED PROPANE AND THIS GAS SYSTEM IS 2.0 PSI
 NATURAL GAS. THE CORRECT SIZING TABLES FOR THIS SYSTEM
 ARE 402.4(3) SCH 40, 402.4(17) CSST, AND 402.4(21) PE.
 ALSO PLEASE DELETE THE FOLLOWING "3/4" POLYETHYLENE
 PLASTIC PIPE LENGTH (FT) 100' MAX. CAPACITY 1,801,000
 BTUH" BECAUSE IT IS ALSO FOR 2.0 PSI UNDILUTED PROPANE
 AND THIS SYSTEM IS 2.0 PSI NATURAL GAS. PLEASE CORRECT
 AND RESUBMIT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721