2007-02-20 14:54:42REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW FOR THE SUBMITTED REVISION:
  
 1. THE GENERATOR BTU LOAD OF 343,000 IS INDICATED
 WRONG ON SHEET E-5 ON THE REVISION, THE CORRECT
 GENERATOR BTU LOAD THAT IS APPROVED FOR THE PERMIT ON
 THE STANDBY GENERATOR OWNER'S MANUAL ON PAGE 6-1,AND
 PRINTS IS 380,000 BTU'S. PLEASE CORRECT AND RESUBMIT.
  
 2. THE MP REGULATOR OF 325-5AL INDICATED ON SHEET E-5
 FOR THE GENERATOR ON THE REVISION IS WRONG. THE CORRECT
 MP REGULATOR FOR THE GENERATOR IS A 325-7L. PLEASE
 REFERENCE THE SUBMITTED MAXITROL MANUFACTURER SHEETS,
 PAGE THREE (3) MAXIMUM INDIVIDUAL LOAD INDICATING THIS.
 PLEASE CORRECT AND RESUBMIT.
  
 3. THE MP REGULATOR OF 325-31 FOR THE STOVE ON SHEET
 E-5 IS WRONG ON THE REVISION. THE CORRECT MP REGULATOR
 FOR THE STOVE IS A 325-3L. PLEASE CORRECT AND
 RESUBMIT.
  
 4. SHEET E-5 GAS ISOMETRIC: PLEASE CLARIFY ON THE
 RESUBMITTED REVISION IF THE GAS PIPE INDICATED FOR THE
 STOVE IS UNDERGROUND OR IF IT IS IN A CRAWL SPACE. IF
 THE GAS PIPE IS UNDERGROUND A SLEEVE IS REQUIRED AND
 NEEDS TO BE INDICATED ON THE RESUBMITTED REVISION PER
 FBC-2004 FUEL GAS, SECTION 404.6 PIPING IN SOLID FLOORS
 AND SECTION 404.11 PIPING UNDERGROUND BENEATH BUILDINGS
 OR IF THE GAS PIPE IS IN A CRAWL SPACE PLEASE INDICATE
 THIS ON THE RESUBMITTED REVISION AND THAT THE PIPE WILL
 BE STRAPPED PER FBC-2004 FUEL GAS, SECTION 407.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  