Plan Review Notes
Plan Review Notes For Permit 06070917
Permit Number 06070917
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-12 12:37:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THIS REVIEW IS FOR THE BUILDING SHELL
 ONLY. ALL ISSUES CONCERNING MINIMUM
 FIXTURES REQUIRED, ACCESSIBLILTY AND
 FAIR HOUSING SHALL BE ADDRESSED AT THE
 TIME OF BUILD OUT FOR ALL 5 FLOORS.
 ******INFORMATIONAL ONLY--OK
  
 2. OK
  
 3. SUBMIT A CONDENSATE RISER DIAGRAM.
 SHOW ALL PIPE SIZES, AND SHOW COMPLIANCE
 WITH SECTION 1506.3, DISCHARGE AT LEAST
 1FT AWAY FROM THE STRUCTURE SIDEWALL.
 SECTION 106.3.5.1.3.
 ******RESPONSE NOTED, BUT THE CONDENSATE SHALL EXIT THE
 BUILDING SEPARATELY, AND CAN CONNECT TO THE STORM
 OUTSIDE THE BUILDING, BUT MUST HAVE A RELIEF VENT
 INSTALLED AS THE CONDENSATE EXITS THE BUILDING.
  
 4. OK
  
 5. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]