| Plan Review Notes For Permit 06070917 |
| Permit Number |
06070917 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-02 11:19:29 | ***DENIED*** | | | | | | PLEASE NOTE THAT MOST OF THE PREVIOUS FIRE REVIEW | | | COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE THE | | | FOLLOWING: | | | | | | 1) COMMENT ACKNOWLEDGED HOWEVER PLEASE INDICATE | | | LOCATION OF EXTINGUISHERS ON DRAWINGS. | | | | | | 2) OK | | | | | | 3) OK MORE DETAILS REGARDING THE DOUBLE DETCTOR CHECK | | | ASSEMBLY WILL BE REQUIRED WITH FIRE SPRINKLER | | | SUBMITTAL. | | | | | | 4) OK | | | | | | 5) PLEASE NOTE THAT THE ADOPTED EDITION FOR FIRE PUMPS | | | IS 2003. PLANS STILL SHOW 1999. | | | | | | 6) OK | | | | | | 7) OK ADDED | | | | | | 8) OK NEW FIRE DEPARTMENTS CONNECTIONS SHALL HAVE KNOX | | | LOCKING CAPS. | | | | | | 9) OK | | | | | | 10) OK | | | | | | 11) OK | | | | | | 12) ACCESSIBLE ENTRY IS CALLED OUT. PLEASE VERIFY IF | | | THIS IS A KNOX BOX USING CITY OF WEST PALM BEACH | | | STANDARD. | | | | | | 13) OK | | | | | | 14) OK | | | | | | 15) OK | | | | | | 16) OK | | | | | | PLEASE SEE BUILDING REVIEW COMMENTS REGARDING WATER | | | CURTAIN SPRINKLER REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | |
|