Plan Review Notes
Plan Review Notes For Permit 06070917
Permit Number 06070917
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-07 18:43:58*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES BASED
 ON REVISED PLANS OR DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE THIS PERMIT WAS APPLIED FOR BEFORE
 THE NEW CODE CHANGE OF DECEMBER 8TH, 2006. PLEASE SEE
 THE VERSION SUBMITTED WENT INTO AFFECT ON THAT DATE.
 PLEASE SEE THE MISSING SIGNATURE FROM THE OWNER AGENT
 AS PRINTED ON SHEET 2.
 PLEASE SEE THE NUMBER OF FIXTURES, TYPE AND WATTAGE OF
 FIXTURES DOES NOT MATCH WITH PLANS.
 PLEASE SEE PLANS INDICATE AUTOMATED LIGHTING CONTROLS,
 YET CALCULATIONS INDICATE MANUAL ON/OFF. THIS IS NOT
 POSSIBLE WITH CONTROLS AS SHOWN.
 PLEASE SEE ROOMS WHICH ONLY STANDARD SWITCH(S) IS BEING
 SHOWN.
 PLEASE SEE NO EXTERIOR LIGHTING IS ENTERED ON
 CALCULATIONS.
 PLEASE CLARIFY THE LIGHTING AS SHOWN FOR MAXIMUM
 LIGHTING POWER DENSITIES.
 PLEASE SEE THE 2004 FBC W/ 2005 REVISIONS CHAPTER 13.
 13-415.1.ABC.1.1, .1.2, 13-415.1.AB1.1, 13-415.2
  
 2) NOTE: PLEASE SEE MISSING AN EMERGENCY BATTERY BACK
 UP FIXTURE IN THE ELEVATOR EQUIPMENT ROOM. THIS COMMENT
 WAS NOT PLACED ON PREVIOUS REVIEW HOWEVER IS REQUIRED.
 PLEASE INDICATE SOME OF BATTERY BACK UP FIXTURE.
 700.16, 700.12E, LS 101 7.8, 7.9
 AND STATE ELEVATOR CODE.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED
 PHOTO-METRICS FOR STAIRS UNDER NORMAL AND UNDER
 EMERGENCY. PLEASE SEE LEVELS UNDER EMERGENCY WERE THE
 ONLY ONES SUBMITTED. COULD NOT LOCATE LEVELS UNDER
 NORMAL. PLEASE SEE BOTH STAIRS ARE LABELED THE SAME.
 PLEASE SEE THE ONE STAIRWAY DOES NOT MEET THE MINIMUM
 LEVELS REQUIRED PER THE LIFE SAFETY CODE UNDER
 EMERGENCY CONDITIONS. PLEASE SEE AS NO NORMAL LIGHTING
 LEVELS WERE SUBMITTED, NO REVIEW OF THESE COULD BE DONE
 AT THIS TIME.
 LS 101 2003, 7.8.1.3, 7.9.2.2
  
 4) NOTE: PLEASE SEE POWER PLANS ARE STILL SHOWING
 PANELS ON EACH FLOOR, HOWEVER PLEASE SEE THESE ARE NOT
 IDENTIFIED OR ON ELECTRICAL RISER. IF THESE ARE
 "FUTURE" PLEASE INDICATE OR NOTE AS FUTURE. PLEASE
 INCLUDE ANY CONDUITS.
 PLEASE SEE THERE ARE MANY SHEETS SUBMITTED AS *POWER
 PLANS* YET THERE IS NO ACTUAL ELECTRICAL BEING SHOWN ON
 THESE SHEETS ?
 IF THESE ARE GOING TO BE INSTALLED AT THIS TIME, PLEASE
 LABEL AND COMPLETE RISER.
 215.5, 230,240, 310, ETC
 106.1.2 FBC
  
 5) NOTE: PLEASE SEE THE LABELING OF THE PANEL FOR HOUSE
 PANELS DO NOT CORRELATE WITH PLANS AND RISER. PLEASE
 SEE THE RISER WHICH CONTAINS A DIFFERENT DESIGNATION
 FOR EACH. PLEASE SEE THE HOUSE PANEL *HB* AS SHOWN ON
 SCHEDULE INDICATES THIS PANEL FEEDING *HA* WHICH RISER
 ACTUALLY HAS THIS REVERES AND LABELED AS LA AND LB
 PANELS.
 PLEASE SEE THE *HOUSE PANELS* ARE STILL BEING SHOWN IN
 WHAT IS SHOWN AS RETAIL TENANT SPACE WHICH IS NOT
 PERMITTED 240.24. (SEPARATE HOUSE ELECTRIC ROOM CAN BE
 CREATED, MOVE EQUIPMENT, OR SOME OTHER CHANGE)
 PLEASE SEE ALL CIRCUITING ON PLANS FOR EACH OF THESE
 PANELS CAN NOT CORRELATE AT THIS TIME FOR DESIGNATION
 AND EACH PANEL.
 PLEASE SEE THE LIGHTING CONTACTOR PANEL WHICH ALSO
 NEEDS COORDINATION FOR EACH AND CIRCUITING.
 PLEASE SEE 408.4, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE CLARIFY *NOTE #10 * ON THE ELEVATOR
 DISCONNECT AS THIS NOTE PERTAINS TO GROUNDING OF SORTS.
 THIS DOES NOT SEEM TO APPLY AT THIS LOCATION?
 FBC 106.1.2
  
 7) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTOR FROM THE MAIN DISCONNECT FOR HOUSE PANEL
 LAI.
 250.110, 250.122.
  
 8) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC RESPONSE MENTIONS TO SEE NOTE ON
 SHEET E6.1, HOWEVER NO NOTE COULD BE FOUND ON SHEET.
 PLEASE ADJUST.
  
 9) NOTE: PLEASE KNOW *ALLEY WAY* IS TO BE VERIFIED FOR
 VEHICLE TRAFFIC FOR SERVICE DROPS, AS THIS OFFICE HAS
 SEEN VEHICULAR TRAFFIC AND ANY HEIGHT WILL BE AT
 CONTRACTORS RISK AS UPON INSPECTION THIS MAY BE
 REQUIRED TO BE INCREASED IF NOT PREVIOUSLY NOTED ON
 PLANS.
 PLEASE PLACE A NOTE AT MINIMUM ON PLANS FOR 230.24
  
 10) NOTE: PLEASE SEE THE MAIN AIC RATING FOR MCA IS
 NOTED AS 65K, WILL THIS BE THE SAME FOR ALL TENANT
 BREAKERS AS SHOWN?
 110.9.
 FBC 106.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]