| 2007-06-07 18:43:58 | *** UNSAT2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES BASED |
| | ON REVISED PLANS OR DOCUMENTS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE THIS PERMIT WAS APPLIED FOR BEFORE |
| | THE NEW CODE CHANGE OF DECEMBER 8TH, 2006. PLEASE SEE |
| | THE VERSION SUBMITTED WENT INTO AFFECT ON THAT DATE. |
| | PLEASE SEE THE MISSING SIGNATURE FROM THE OWNER AGENT |
| | AS PRINTED ON SHEET 2. |
| | PLEASE SEE THE NUMBER OF FIXTURES, TYPE AND WATTAGE OF |
| | FIXTURES DOES NOT MATCH WITH PLANS. |
| | PLEASE SEE PLANS INDICATE AUTOMATED LIGHTING CONTROLS, |
| | YET CALCULATIONS INDICATE MANUAL ON/OFF. THIS IS NOT |
| | POSSIBLE WITH CONTROLS AS SHOWN. |
| | PLEASE SEE ROOMS WHICH ONLY STANDARD SWITCH(S) IS BEING |
| | SHOWN. |
| | PLEASE SEE NO EXTERIOR LIGHTING IS ENTERED ON |
| | CALCULATIONS. |
| | PLEASE CLARIFY THE LIGHTING AS SHOWN FOR MAXIMUM |
| | LIGHTING POWER DENSITIES. |
| | PLEASE SEE THE 2004 FBC W/ 2005 REVISIONS CHAPTER 13. |
| | 13-415.1.ABC.1.1, .1.2, 13-415.1.AB1.1, 13-415.2 |
| | |
| | 2) NOTE: PLEASE SEE MISSING AN EMERGENCY BATTERY BACK |
| | UP FIXTURE IN THE ELEVATOR EQUIPMENT ROOM. THIS COMMENT |
| | WAS NOT PLACED ON PREVIOUS REVIEW HOWEVER IS REQUIRED. |
| | PLEASE INDICATE SOME OF BATTERY BACK UP FIXTURE. |
| | 700.16, 700.12E, LS 101 7.8, 7.9 |
| | AND STATE ELEVATOR CODE. |
| | |
| | 3) NOTE: PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED |
| | PHOTO-METRICS FOR STAIRS UNDER NORMAL AND UNDER |
| | EMERGENCY. PLEASE SEE LEVELS UNDER EMERGENCY WERE THE |
| | ONLY ONES SUBMITTED. COULD NOT LOCATE LEVELS UNDER |
| | NORMAL. PLEASE SEE BOTH STAIRS ARE LABELED THE SAME. |
| | PLEASE SEE THE ONE STAIRWAY DOES NOT MEET THE MINIMUM |
| | LEVELS REQUIRED PER THE LIFE SAFETY CODE UNDER |
| | EMERGENCY CONDITIONS. PLEASE SEE AS NO NORMAL LIGHTING |
| | LEVELS WERE SUBMITTED, NO REVIEW OF THESE COULD BE DONE |
| | AT THIS TIME. |
| | LS 101 2003, 7.8.1.3, 7.9.2.2 |
| | |
| | 4) NOTE: PLEASE SEE POWER PLANS ARE STILL SHOWING |
| | PANELS ON EACH FLOOR, HOWEVER PLEASE SEE THESE ARE NOT |
| | IDENTIFIED OR ON ELECTRICAL RISER. IF THESE ARE |
| | "FUTURE" PLEASE INDICATE OR NOTE AS FUTURE. PLEASE |
| | INCLUDE ANY CONDUITS. |
| | PLEASE SEE THERE ARE MANY SHEETS SUBMITTED AS *POWER |
| | PLANS* YET THERE IS NO ACTUAL ELECTRICAL BEING SHOWN ON |
| | THESE SHEETS ? |
| | IF THESE ARE GOING TO BE INSTALLED AT THIS TIME, PLEASE |
| | LABEL AND COMPLETE RISER. |
| | 215.5, 230,240, 310, ETC |
| | 106.1.2 FBC |
| | |
| | 5) NOTE: PLEASE SEE THE LABELING OF THE PANEL FOR HOUSE |
| | PANELS DO NOT CORRELATE WITH PLANS AND RISER. PLEASE |
| | SEE THE RISER WHICH CONTAINS A DIFFERENT DESIGNATION |
| | FOR EACH. PLEASE SEE THE HOUSE PANEL *HB* AS SHOWN ON |
| | SCHEDULE INDICATES THIS PANEL FEEDING *HA* WHICH RISER |
| | ACTUALLY HAS THIS REVERES AND LABELED AS LA AND LB |
| | PANELS. |
| | PLEASE SEE THE *HOUSE PANELS* ARE STILL BEING SHOWN IN |
| | WHAT IS SHOWN AS RETAIL TENANT SPACE WHICH IS NOT |
| | PERMITTED 240.24. (SEPARATE HOUSE ELECTRIC ROOM CAN BE |
| | CREATED, MOVE EQUIPMENT, OR SOME OTHER CHANGE) |
| | PLEASE SEE ALL CIRCUITING ON PLANS FOR EACH OF THESE |
| | PANELS CAN NOT CORRELATE AT THIS TIME FOR DESIGNATION |
| | AND EACH PANEL. |
| | PLEASE SEE THE LIGHTING CONTACTOR PANEL WHICH ALSO |
| | NEEDS COORDINATION FOR EACH AND CIRCUITING. |
| | PLEASE SEE 408.4, 310.16, 240.4 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE CLARIFY *NOTE #10 * ON THE ELEVATOR |
| | DISCONNECT AS THIS NOTE PERTAINS TO GROUNDING OF SORTS. |
| | THIS DOES NOT SEEM TO APPLY AT THIS LOCATION? |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THE MAIN DISCONNECT FOR HOUSE PANEL |
| | LAI. |
| | 250.110, 250.122. |
| | |
| | 8) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC RESPONSE MENTIONS TO SEE NOTE ON |
| | SHEET E6.1, HOWEVER NO NOTE COULD BE FOUND ON SHEET. |
| | PLEASE ADJUST. |
| | |
| | 9) NOTE: PLEASE KNOW *ALLEY WAY* IS TO BE VERIFIED FOR |
| | VEHICLE TRAFFIC FOR SERVICE DROPS, AS THIS OFFICE HAS |
| | SEEN VEHICULAR TRAFFIC AND ANY HEIGHT WILL BE AT |
| | CONTRACTORS RISK AS UPON INSPECTION THIS MAY BE |
| | REQUIRED TO BE INCREASED IF NOT PREVIOUSLY NOTED ON |
| | PLANS. |
| | PLEASE PLACE A NOTE AT MINIMUM ON PLANS FOR 230.24 |
| | |
| | 10) NOTE: PLEASE SEE THE MAIN AIC RATING FOR MCA IS |
| | NOTED AS 65K, WILL THIS BE THE SAME FOR ALL TENANT |
| | BREAKERS AS SHOWN? |
| | 110.9. |
| | FBC 106.1.2 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |