Plan Review Notes
Plan Review Notes For Permit 06070917
Permit Number 06070917
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-29 17:13:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)ADDRESSED.PLEASE KEEP THE STAMPED SHEET AND
 RECEIPT FOR IMPACT FEES IN THE PACKAGE.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 3-4.) ADDRESSED. PLEASE KEEP THE THRESHOLD INSPECTION
 PLAN (3 ORIGINALS, ONE WITH EACH SET) IN THE PACKAGE AS
 SUBMITTED.
  
 5.) PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 2ND REVIEW - THIS HAS NOT BEEN DONE.PLEASE BE ADVISED
 THAT THE PERMIT CANNOT BE ISSUED THE INSPECTOR AND THE
 INSPECTION PLAN HAS BEEN APPROVED BY HAROLD PISKURA.
  
 6-15.) ADDRESSED.
  
 16.)PARTIALLY ADDRESSED.ARCHITECT HAS ADDRESSED
 THIS COMMENT AND OTHERS BY PROPOSING TO INSTALL A WATER
 CURTAIN INSTALLED IN ACCORDANCE WITH NFPA13.THE
 SPRINKLER HEAD SPECIFICATIONS PROVIDED (UPON REVIEWER'S
 REQUEST, SUBMITTED VIA EMAIL BY KATHY VUYOVICK OF
 TOMAC) REQUIRE A NON-OPERABLE WINDOW.THIS SPEC CAN BE
 SEEN AT WWW.TYCO-FIRE.COM, SPRINKLER TFP620 AND ALSO
 THE SPEC IS ATTACHED.PLEASE NOTE THE FOLLOWING:
  
 A. A NON-OPERABLE WINDOW IS REQUIRED.OPERABLE WINDOWS
 ARE SHOWN ON THE PLAN.
  
 B. WINDOW SPRINKLERS ARE NOT LISTED TO PROTECT WINDOWS
 WHEN INTERMEDIATE HORIZONTAL MULLIONS ARE PRESENT. THIS
 WAS CONFIRMED WITH THE SPRINKLER COMPANY THAT THIS
 APPLIES TO APPLIED MUNTINS AS WELL AS STRUCTURAL
 MULLIONS OR WINDOW MEETING RAILS.SHEET S10 SHOWS
 HORIZONTAL MULLIONS ON ALL WINDOWS.
  
 C. S10, ELEVATIONS CONFLICT WITH FIRE SPRINKLER LAYOUT;
 MULTIPLE HEADS SHOWN PER WINDOW ON THE SPRINKLER PLANS,
 ONLY ONE HEAD SHOWN ON ELEVATIONS.
  
 D. FS2.1, THE WATER CURTAIN SPRINKLER HEADS ARE 3FT
 APART, 6FT DISTANCE REQUIRED UNLESS A MULLION CAN ACT
 AS A BAFFLE.PROVIDE A DETAIL SHOWING THAT THE
 PROPOSED MULLION WILL COMPLY WITH THE REQUIREMENT (FOR
 THE PENDANT VERTICAL SIDEWALL, EXTENDS TO THE BACK OF
 SPRINKLER DEFLECTOR OR, FOR THE HORIZONTAL SIDEWALL,
 MULLION EXTENDS TO THE SPRINKLER WRENCH FLAT).SEE
 PAGE 3 OF THE SPRINKLER SPECIFICATION.
  
 E. FS2.3, SPRINKLER HEADS ARE 4FT AND 5FT APART, NO
 MULLION; 6' DISTANCE REQUIRED.
  
 F. PAGE 3 OF SPRINKLER SPECS, MINIMUM CLEARANCE FROM
 FACE OF GLASS TO COMBUSTIBLE MATERIALS; SHOW COMPLIANCE
 ON THE PLAN AS TO HOW THIS WILL BE ENFORCED.
  
 G. FS2.1, THE WINDOW SPRINKLER HEADS ARE TO BE LOCATED
 A MINIMUM OF 6FT FROM STANDARD SPRINKLER HEADS.SEE
 NORTHWEST CORNER, NORTH SIDE.CHECK ALL.
  
 H. S10 AND ARCHITECTURAL SHEETS SHOW VERTICAL MULLIONS,
 NORTH AND SOUTH ELEVATIONS, WHICH ARE NOT SHOWN ON THE
 FS DRAWINGS.FS DRAWINGS ARE TO BE CONSISTENT IF A
 WATER CURTAIN IS USED.S10 AND ARCHITECTURAL SHEETS
 SHOW WATER CURTAIN SPRINKLER HEADS LOCATIONS ARE
 INCORRECT, SEE FS SHEETS.
  
 17.)PROVIDE CALCULATIONS FOR OPENINGS ALLOWED.I AM
 UNABLE TO DETERMINE HOW YOU?VE ARRIVED AT THE NUMBERS.
 FOR INSTANCE, EAST WALL 4TH AND 5TH FLOORS SHOW 8%
 OPENINGS.THIS WOULD REQUIRE A 625SF WALL BUT THE WALL
 IS APPROXIMATELY 47FT X 10FT.FLOOR/CEILING ASSEMBLIES
 SHOULD BE EXCLUDED FROM WALL AREA, AND THE OPENINGS
 SHOULD BE EQUALLY SPACED, SEE COMMENTARY SENT WITH
 FIRST REVIEW.
  
 A. SEE PREVIOUS LIST, SOUTH ELEVATION, NO OPENINGS
 ALLOWED.SEE FBC EB601.3, FBC TABLE 704.8.THE WATER
 CURTAIN DOES NOT WAIVE THIS LIMITATION.
  
 B. NORTH WALL IS LIMITED TO 25% OF OPENINGS FOR A FULLY
 SPRINKLERED BUILDING.SECOND FLOOR SHOWS 30%, A3.1A.
  
 C. WEST WALL, THE 4TH AND 5TH FLOORS
 APPEAR TO BE BE OVER 30FT FROM THE
 PROPERTY LINE (CENTERLINE OF OLIVE AVE),
 NO LIMITATIONS ON OPENINGS.THE 1ST
 THROUGH 3RD STORY WALL APPEARS TO BE
 APPROXIMATELY 26% OPENINGS, NO
 PROTECTION REQUIRED.
  
 D. EAST WALL, SEE OTHER COMMENTS.NOTE THAT 25%
 OPENINGS ALLOWED FOR FULLY SPRINKLERED BUILDING, FBC
 TABLE 704.8.
  
 18-22.) ADDRESSED.
  
 22.)PARAPET CONSTRUCTION IS TO COMPLY
 WITH FBC704.11.1.SHOW FIRE RESISTANCE
 FOR PARAPETS AS REQUIRED.
  
 2ND REVIEW, THIS WAS ADDRESSED IN THE RESPONSE LETTER,
 BUT WAS A NOTE PLACED ON THE PLAN REGARDING THE
 EXISTING CONDITIONS?IF IT WAS, PLEASE ADVISE AS TO
 HOW THE COMMENT WAS ADDRESSED ON THE PLAN, AND IF NOT,
 PLEASE NOTE ON THE PLAN.
  
 23.) ADDRESSED.
  
 24.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.THIS MUST BE DONE PRIOR TO PERMIT
 ISSUANCE.THIS MAY BE DONE WITH A SHOP DRAWING REVIEW
 STAMP, A LETTER, OR INCORPORATING THE INFORMATION INTO
 THE PLAN.
  
 25.)ALL PRODUCT APPROVALS REQUIRED PRIOR TO PERMIT
 ISSUANCE.
  
 26.)PRODUCT APPROVALS FOR THE LOUVERS, AND MECHANICAL
 STANDS
 WERE NOT SUBMITTED.
  
 THE DAYBAR DOOR PRODUCT APPROVALS ARE NOT PRINTED
 PROPERLY.THE DESIGN PRESSURES OF +-90 WAS CUT OFF.
 SEE THE SPEC SHEETS, INCOMPLETE.PLEASE PROVIDE A
 COMPLETE PRODUCT APPROVAL.
  
 27.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 WILL BE ISSUED USING THE NOA. WWW.FLORIDABUILDING.ORG
  
 NOT ADDRESSED.THIS IS REQUIRED.
  
 THE CGI 360 SINGLE HUNG WINDOW, SHEET 1 OF 6, USES A
 STRESS INCREASE WHICH IS NOT ALLOWED.IF A FLORIDA
 STATE PRODUCT APPROVAL IS NOT AVAILABLE FOR THIS
 PRODUCT, AND YOU WOULD LIKE A LOCAL PRODUCT APPROVAL TO
 BE ISSUED, PROVIDE THE LETTER WHICH THIS MANUFACTURER
 PROVIDED MIAMIDADE TO SHOW COMPLIANCE WITH FBC2004
 (CALCULATIONS WITHOUT THE STRESS INCREASE).
  
 PLEASE PROVIDE MORE INFORMATION IN REGARDS TO THE
 WINDOWS; CONFIGURATION OF WINDOWS WITH MULLIONS.IT IS
 NOT CLEAR FROM THE PLANS IF THE WINDOWS ARE SEPARATED
 BY MULLIONS OR IF THEY ARE APPLIED MUNTINS.
  
 28-30.) ADDRESSED.
  
 31.)FROM PREVIOUS LIST; REMOVABLE SHUTTERS ON THE
 FIRST
 FLOOR MUST BE APPROVED BY THE BUILDING
 OFFICIAL.THE NOTE HAS BEEN REVISED TO STATE THAT
 REMOVABLE SHUTTERS WILL BE USED ON THE FIRST FLOOR
 ONLY.SUBMIT PRODUCT APPROVALS, INSTALLATION SCHEDULE
 (ATTACHED) AND PRIOR TO RESUBMITTAL OF PLANS SUBMIT A
 HURRICANE SHUTTER INSTALLATION PLAN.THIS MUST BE
 APPROVED PRIOR TO PERMIT ISSUANCE.FAILURE TO ADDRESS
 THIS ITEM WILL RESULT IN PERMIT DELAYS.THIS IS NOT
 REQUIRED IF YOU ARE USING IMPACT GLASS ON THE FIRST
 FLOOR AS WELL AS OTHER FLOORS.
  
 32-33.) ADDRESSED.
  
 34.)TENANT BUILDOUTS ARE NOTED AS A
 SEPARATE PERMIT.THIS PERMIT WILL BE AN
 AT RISK PERMIT AS CODE COMPLIANCE FOR
 ALL FLOORS CANNOT BE DETERMINED.SHELL
 BUILDING ONLY.
  
 35.)PROVIDE DESIGN CRITERIA AND A
 DETAIL FOR THE GUARDRAILS ON THE
 BALCONIES (TWO TYPES) AND STAIRS,
 FBC1607.7, FBC1012.
  
 A3.1 DOES NOT SHOW THE OPENING SIZES AT THE BOTTOM AND
 SIDES.IT DOES NOT STATE DESIGN LOAD PER FBC1607.7.
 DESIGNER IS TO STATE DESIGN CRITERIA; SHOPS WILL FOLLOW
 THE DESIGN CRITERIA.12-A2.4, STATE DESIGN CRITERIA
 AND PROVIDE OPENING DIMENSIONS.PROVIDE STAIR GUARD
 DETAIL.S4 CITES A CODE SECTION FOR THE HANDRAIL.
 PLEASE PROVIDE A DETAIL AND STATE DESIGN CRITERIA
 FBC1607.7.
  
 36.)PARTITIONS AND PENETRATIONS ARE TO
 COMPLY WITH FBC1207, SOUND TRANSMISSION.
  
 THERE IS A NOTE STATING THAT THEY ARE TO COMPLY. PLEASE
 STATE DESIGN CRITERIA.
  
 37-39.) ADDRESSED.
  
 40.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1802.2.ORIGINALS REQUIRED (ORIGINAL
 SIGNATURE, PHOTOCOPIES SUBMITTED).
  
 41.)ADDRESSED.
  
 42.)VENTS ARE SHOWN ON THE PLAN, M2.1.
 SEE ABOVE COMMENTS IN REGARDS TO THE
 FIRE RATING OF THE WALL AND REQUIRED
 PROTECTED OPENINGS.THESE VENTS WERE
 NOT CALCULATED IN THE AMOUNT OF
 ALLOWABLE OPENINGS AS THEY ARE NOT SHOWN
 ON THE ELEVATIONS.PLEASE ADDRESS.
  
 2ND REVIEW, NOT ADDRESSED.THE VENTS ARE TO BE SHOWN
 ON THE ARCHITECTURAL DRAWINGS AND INCLUDED IN
 OPENINGS.
  
  
 43.)M5 REFERS TO FBC2001, GOVERNING
 CODE IS FBC2004.
  
 2ND REVIEW, WAS ADDRESSED IN ONE PLACE BUT M5.1 STILL
 STATES 2001.
  
 44.) ENERGY CALCS SHOW AREAS OF 305 AND 260 SF.
 CLARIFY.
  