| 2007-06-29 17:13:32 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB |
| | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | |
| | 1.)ADDRESSED.PLEASE KEEP THE STAMPED SHEET AND |
| | RECEIPT FOR IMPACT FEES IN THE PACKAGE. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS, |
| | FS713.13. |
| | |
| | 3-4.) ADDRESSED. PLEASE KEEP THE THRESHOLD INSPECTION |
| | PLAN (3 ORIGINALS, ONE WITH EACH SET) IN THE PACKAGE AS |
| | SUBMITTED. |
| | |
| | 5.) PLEASE ARRANGE WITH HAROLD PISKURA |
| | (INSPECTION SERVICES MANAGER - TEL: |
| | 561 805 6711), A MEETING INVOLVING THE |
| | OWNER, RESIDENT INSPECTOR, JOB |
| | INSPECTOR, CONTRACTOR AND ENGINEER. |
| | |
| | 2ND REVIEW - THIS HAS NOT BEEN DONE.PLEASE BE ADVISED |
| | THAT THE PERMIT CANNOT BE ISSUED THE INSPECTOR AND THE |
| | INSPECTION PLAN HAS BEEN APPROVED BY HAROLD PISKURA. |
| | |
| | 6-15.) ADDRESSED. |
| | |
| | 16.)PARTIALLY ADDRESSED.ARCHITECT HAS ADDRESSED |
| | THIS COMMENT AND OTHERS BY PROPOSING TO INSTALL A WATER |
| | CURTAIN INSTALLED IN ACCORDANCE WITH NFPA13.THE |
| | SPRINKLER HEAD SPECIFICATIONS PROVIDED (UPON REVIEWER'S |
| | REQUEST, SUBMITTED VIA EMAIL BY KATHY VUYOVICK OF |
| | TOMAC) REQUIRE A NON-OPERABLE WINDOW.THIS SPEC CAN BE |
| | SEEN AT WWW.TYCO-FIRE.COM, SPRINKLER TFP620 AND ALSO |
| | THE SPEC IS ATTACHED.PLEASE NOTE THE FOLLOWING: |
| | |
| | A. A NON-OPERABLE WINDOW IS REQUIRED.OPERABLE WINDOWS |
| | ARE SHOWN ON THE PLAN. |
| | |
| | B. WINDOW SPRINKLERS ARE NOT LISTED TO PROTECT WINDOWS |
| | WHEN INTERMEDIATE HORIZONTAL MULLIONS ARE PRESENT. THIS |
| | WAS CONFIRMED WITH THE SPRINKLER COMPANY THAT THIS |
| | APPLIES TO APPLIED MUNTINS AS WELL AS STRUCTURAL |
| | MULLIONS OR WINDOW MEETING RAILS.SHEET S10 SHOWS |
| | HORIZONTAL MULLIONS ON ALL WINDOWS. |
| | |
| | C. S10, ELEVATIONS CONFLICT WITH FIRE SPRINKLER LAYOUT; |
| | MULTIPLE HEADS SHOWN PER WINDOW ON THE SPRINKLER PLANS, |
| | ONLY ONE HEAD SHOWN ON ELEVATIONS. |
| | |
| | D. FS2.1, THE WATER CURTAIN SPRINKLER HEADS ARE 3FT |
| | APART, 6FT DISTANCE REQUIRED UNLESS A MULLION CAN ACT |
| | AS A BAFFLE.PROVIDE A DETAIL SHOWING THAT THE |
| | PROPOSED MULLION WILL COMPLY WITH THE REQUIREMENT (FOR |
| | THE PENDANT VERTICAL SIDEWALL, EXTENDS TO THE BACK OF |
| | SPRINKLER DEFLECTOR OR, FOR THE HORIZONTAL SIDEWALL, |
| | MULLION EXTENDS TO THE SPRINKLER WRENCH FLAT).SEE |
| | PAGE 3 OF THE SPRINKLER SPECIFICATION. |
| | |
| | E. FS2.3, SPRINKLER HEADS ARE 4FT AND 5FT APART, NO |
| | MULLION; 6' DISTANCE REQUIRED. |
| | |
| | F. PAGE 3 OF SPRINKLER SPECS, MINIMUM CLEARANCE FROM |
| | FACE OF GLASS TO COMBUSTIBLE MATERIALS; SHOW COMPLIANCE |
| | ON THE PLAN AS TO HOW THIS WILL BE ENFORCED. |
| | |
| | G. FS2.1, THE WINDOW SPRINKLER HEADS ARE TO BE LOCATED |
| | A MINIMUM OF 6FT FROM STANDARD SPRINKLER HEADS.SEE |
| | NORTHWEST CORNER, NORTH SIDE.CHECK ALL. |
| | |
| | H. S10 AND ARCHITECTURAL SHEETS SHOW VERTICAL MULLIONS, |
| | NORTH AND SOUTH ELEVATIONS, WHICH ARE NOT SHOWN ON THE |
| | FS DRAWINGS.FS DRAWINGS ARE TO BE CONSISTENT IF A |
| | WATER CURTAIN IS USED.S10 AND ARCHITECTURAL SHEETS |
| | SHOW WATER CURTAIN SPRINKLER HEADS LOCATIONS ARE |
| | INCORRECT, SEE FS SHEETS. |
| | |
| | 17.)PROVIDE CALCULATIONS FOR OPENINGS ALLOWED.I AM |
| | UNABLE TO DETERMINE HOW YOU?VE ARRIVED AT THE NUMBERS. |
| | FOR INSTANCE, EAST WALL 4TH AND 5TH FLOORS SHOW 8% |
| | OPENINGS.THIS WOULD REQUIRE A 625SF WALL BUT THE WALL |
| | IS APPROXIMATELY 47FT X 10FT.FLOOR/CEILING ASSEMBLIES |
| | SHOULD BE EXCLUDED FROM WALL AREA, AND THE OPENINGS |
| | SHOULD BE EQUALLY SPACED, SEE COMMENTARY SENT WITH |
| | FIRST REVIEW. |
| | |
| | A. SEE PREVIOUS LIST, SOUTH ELEVATION, NO OPENINGS |
| | ALLOWED.SEE FBC EB601.3, FBC TABLE 704.8.THE WATER |
| | CURTAIN DOES NOT WAIVE THIS LIMITATION. |
| | |
| | B. NORTH WALL IS LIMITED TO 25% OF OPENINGS FOR A FULLY |
| | SPRINKLERED BUILDING.SECOND FLOOR SHOWS 30%, A3.1A. |
| | |
| | C. WEST WALL, THE 4TH AND 5TH FLOORS |
| | APPEAR TO BE BE OVER 30FT FROM THE |
| | PROPERTY LINE (CENTERLINE OF OLIVE AVE), |
| | NO LIMITATIONS ON OPENINGS.THE 1ST |
| | THROUGH 3RD STORY WALL APPEARS TO BE |
| | APPROXIMATELY 26% OPENINGS, NO |
| | PROTECTION REQUIRED. |
| | |
| | D. EAST WALL, SEE OTHER COMMENTS.NOTE THAT 25% |
| | OPENINGS ALLOWED FOR FULLY SPRINKLERED BUILDING, FBC |
| | TABLE 704.8. |
| | |
| | 18-22.) ADDRESSED. |
| | |
| | 22.)PARAPET CONSTRUCTION IS TO COMPLY |
| | WITH FBC704.11.1.SHOW FIRE RESISTANCE |
| | FOR PARAPETS AS REQUIRED. |
| | |
| | 2ND REVIEW, THIS WAS ADDRESSED IN THE RESPONSE LETTER, |
| | BUT WAS A NOTE PLACED ON THE PLAN REGARDING THE |
| | EXISTING CONDITIONS?IF IT WAS, PLEASE ADVISE AS TO |
| | HOW THE COMMENT WAS ADDRESSED ON THE PLAN, AND IF NOT, |
| | PLEASE NOTE ON THE PLAN. |
| | |
| | 23.) ADDRESSED. |
| | |
| | 24.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF |
| | RECORD, FBC*106.3.3.THIS MUST BE DONE PRIOR TO PERMIT |
| | ISSUANCE.THIS MAY BE DONE WITH A SHOP DRAWING REVIEW |
| | STAMP, A LETTER, OR INCORPORATING THE INFORMATION INTO |
| | THE PLAN. |
| | |
| | 25.)ALL PRODUCT APPROVALS REQUIRED PRIOR TO PERMIT |
| | ISSUANCE. |
| | |
| | 26.)PRODUCT APPROVALS FOR THE LOUVERS, AND MECHANICAL |
| | STANDS |
| | WERE NOT SUBMITTED. |
| | |
| | THE DAYBAR DOOR PRODUCT APPROVALS ARE NOT PRINTED |
| | PROPERLY.THE DESIGN PRESSURES OF +-90 WAS CUT OFF. |
| | SEE THE SPEC SHEETS, INCOMPLETE.PLEASE PROVIDE A |
| | COMPLETE PRODUCT APPROVAL. |
| | |
| | 27.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72.IF A |
| | FLORIDA STATE PRODUCT APPROVAL IS NOT |
| | AVAILABLE, PLEASE ADVISE AND A LOCAL |
| | WILL BE ISSUED USING THE NOA. WWW.FLORIDABUILDING.ORG |
| | |
| | NOT ADDRESSED.THIS IS REQUIRED. |
| | |
| | THE CGI 360 SINGLE HUNG WINDOW, SHEET 1 OF 6, USES A |
| | STRESS INCREASE WHICH IS NOT ALLOWED.IF A FLORIDA |
| | STATE PRODUCT APPROVAL IS NOT AVAILABLE FOR THIS |
| | PRODUCT, AND YOU WOULD LIKE A LOCAL PRODUCT APPROVAL TO |
| | BE ISSUED, PROVIDE THE LETTER WHICH THIS MANUFACTURER |
| | PROVIDED MIAMIDADE TO SHOW COMPLIANCE WITH FBC2004 |
| | (CALCULATIONS WITHOUT THE STRESS INCREASE). |
| | |
| | PLEASE PROVIDE MORE INFORMATION IN REGARDS TO THE |
| | WINDOWS; CONFIGURATION OF WINDOWS WITH MULLIONS.IT IS |
| | NOT CLEAR FROM THE PLANS IF THE WINDOWS ARE SEPARATED |
| | BY MULLIONS OR IF THEY ARE APPLIED MUNTINS. |
| | |
| | 28-30.) ADDRESSED. |
| | |
| | 31.)FROM PREVIOUS LIST; REMOVABLE SHUTTERS ON THE |
| | FIRST |
| | FLOOR MUST BE APPROVED BY THE BUILDING |
| | OFFICIAL.THE NOTE HAS BEEN REVISED TO STATE THAT |
| | REMOVABLE SHUTTERS WILL BE USED ON THE FIRST FLOOR |
| | ONLY.SUBMIT PRODUCT APPROVALS, INSTALLATION SCHEDULE |
| | (ATTACHED) AND PRIOR TO RESUBMITTAL OF PLANS SUBMIT A |
| | HURRICANE SHUTTER INSTALLATION PLAN.THIS MUST BE |
| | APPROVED PRIOR TO PERMIT ISSUANCE.FAILURE TO ADDRESS |
| | THIS ITEM WILL RESULT IN PERMIT DELAYS.THIS IS NOT |
| | REQUIRED IF YOU ARE USING IMPACT GLASS ON THE FIRST |
| | FLOOR AS WELL AS OTHER FLOORS. |
| | |
| | 32-33.) ADDRESSED. |
| | |
| | 34.)TENANT BUILDOUTS ARE NOTED AS A |
| | SEPARATE PERMIT.THIS PERMIT WILL BE AN |
| | AT RISK PERMIT AS CODE COMPLIANCE FOR |
| | ALL FLOORS CANNOT BE DETERMINED.SHELL |
| | BUILDING ONLY. |
| | |
| | 35.)PROVIDE DESIGN CRITERIA AND A |
| | DETAIL FOR THE GUARDRAILS ON THE |
| | BALCONIES (TWO TYPES) AND STAIRS, |
| | FBC1607.7, FBC1012. |
| | |
| | A3.1 DOES NOT SHOW THE OPENING SIZES AT THE BOTTOM AND |
| | SIDES.IT DOES NOT STATE DESIGN LOAD PER FBC1607.7. |
| | DESIGNER IS TO STATE DESIGN CRITERIA; SHOPS WILL FOLLOW |
| | THE DESIGN CRITERIA.12-A2.4, STATE DESIGN CRITERIA |
| | AND PROVIDE OPENING DIMENSIONS.PROVIDE STAIR GUARD |
| | DETAIL.S4 CITES A CODE SECTION FOR THE HANDRAIL. |
| | PLEASE PROVIDE A DETAIL AND STATE DESIGN CRITERIA |
| | FBC1607.7. |
| | |
| | 36.)PARTITIONS AND PENETRATIONS ARE TO |
| | COMPLY WITH FBC1207, SOUND TRANSMISSION. |
| | |
| | THERE IS A NOTE STATING THAT THEY ARE TO COMPLY. PLEASE |
| | STATE DESIGN CRITERIA. |
| | |
| | 37-39.) ADDRESSED. |
| | |
| | 40.)PROVIDE A SOILS INVESTIGATION |
| | REPORT, FBC1802.2.ORIGINALS REQUIRED (ORIGINAL |
| | SIGNATURE, PHOTOCOPIES SUBMITTED). |
| | |
| | 41.)ADDRESSED. |
| | |
| | 42.)VENTS ARE SHOWN ON THE PLAN, M2.1. |
| | SEE ABOVE COMMENTS IN REGARDS TO THE |
| | FIRE RATING OF THE WALL AND REQUIRED |
| | PROTECTED OPENINGS.THESE VENTS WERE |
| | NOT CALCULATED IN THE AMOUNT OF |
| | ALLOWABLE OPENINGS AS THEY ARE NOT SHOWN |
| | ON THE ELEVATIONS.PLEASE ADDRESS. |
| | |
| | 2ND REVIEW, NOT ADDRESSED.THE VENTS ARE TO BE SHOWN |
| | ON THE ARCHITECTURAL DRAWINGS AND INCLUDED IN |
| | OPENINGS. |
| | |
| | |
| | 43.)M5 REFERS TO FBC2001, GOVERNING |
| | CODE IS FBC2004. |
| | |
| | 2ND REVIEW, WAS ADDRESSED IN ONE PLACE BUT M5.1 STILL |
| | STATES 2001. |
| | |
| | 44.) ENERGY CALCS SHOW AREAS OF 305 AND 260 SF. |
| | CLARIFY. |
| | |