| Plan Review Notes For Permit 06070917 |
| Permit Number |
06070917 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-24 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. THIS REVIEW IS FOR THE BUILDING SHELL | | | ONLY. ALL ISSUES CONCERNING MINIMUM | | | FIXTURES REQUIRED, ACCESSIBLILTY AND | | | FAIR HOUSING SHALL BE ADDRESSED AT THE | | | TIME OF BUILD OUT FOR ALL 5 FLOORS. | | | | | | 2. SUBMIT A STORM RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, AND INDICATE SQUARE | | | FOOTAGE. SHOW ALL CLEANOUTS REQUIRED BY | | | SECTION 1101.8. SECTION 1106.3.5.1.3. | | | | | | 3. SUBMIT A CONDENSATE RISER DIAGRAM. | | | SHOW ALL PIPE SIZES, AND SHOW COMPLIANCE | | | WITH SECTION 1506.3, DISCHARGE AT LEAST | | | 1FT AWAY FROM THE STRUCTURE SIDEWALL. | | | SECTION 106.3.5.1.3. | | | | | | 4. AN RPZV BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE. SECTION 608.13.2. | | | | | | 5. ALL PLUMBING, ELECTRICAL, MECHANICAL, | | | FIRE SPRINKLER SHEETS. ENGINEER | | | CERTIFICATE OF AUTHORIZATION DOES NOT | | | MATCH THE NUMBER SHOWN IN DBPR WEBSIET. | | | PLEASE INDICATE CERTIFICATE OF | | | AUTHORIZATION IN TITLE BLOCK FOR KAMM | | | CONSULTING. (SEE ATTACHED SHEET FROM | | | DBPR). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|