2006-08-24 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THIS REVIEW IS FOR THE BUILDING SHELL
 ONLY. ALL ISSUES CONCERNING MINIMUM
 FIXTURES REQUIRED, ACCESSIBLILTY AND
 FAIR HOUSING SHALL BE ADDRESSED AT THE
 TIME OF BUILD OUT FOR ALL 5 FLOORS.
  
 2. SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES, AND INDICATE SQUARE
 FOOTAGE. SHOW ALL CLEANOUTS REQUIRED BY
 SECTION 1101.8. SECTION 1106.3.5.1.3.
  
 3. SUBMIT A CONDENSATE RISER DIAGRAM.
 SHOW ALL PIPE SIZES, AND SHOW COMPLIANCE
 WITH SECTION 1506.3, DISCHARGE AT LEAST
 1FT AWAY FROM THE STRUCTURE SIDEWALL.
 SECTION 106.3.5.1.3.
  
 4. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
  
 5. ALL PLUMBING, ELECTRICAL, MECHANICAL,
 FIRE SPRINKLER SHEETS. ENGINEER
 CERTIFICATE OF AUTHORIZATION DOES NOT
 MATCH THE NUMBER SHOWN IN DBPR WEBSIET.
 PLEASE INDICATE CERTIFICATE OF
 AUTHORIZATION IN TITLE BLOCK FOR KAMM
 CONSULTING. (SEE ATTACHED SHEET FROM
 DBPR).
  