Plan Review Notes
Plan Review Notes For Permit 06070917
Permit Number 06070917
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-04 00:00:00PASS PROVISO
 1) PAGE M2.1 AHU #1 PLEASE REFER TO
 SECTION 307.2.3 AUXILIARY AND SECONDARY
 DRAIN SYSTEM.
 2) PLEASE PROVIED MANUFACTURE
 INSTALLATION INSRTUCTIONS FOR MOTORIZED
 DAMPER AT ROUGH INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732