Plan Review Notes
Plan Review Notes For Permit 06070917
Permit Number 06070917
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-08-31 00:00:00***DENIED***
  
 1) PLEASE SHOW LOCATION OF 2A-10B,C
 RATED FIRE EXTINGUISHERS THAT SHALL BE
 MOUNTED NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 2) ELEVATOR TO COMPLY WITH ASME A17.1.
  
 3) DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 BE SECURED WITH CHAIN AND LOCK IN
 ADDITION TO ELECTRONIC SUPERVISION.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS. PLEASE INCLUDE
 CALCULATION AND MANUFACTURER SPEC
 SHEETS.
  
 5) FIRE PUMP TO COMPLY WITH NFPA 20,
 2003 EDITION UNLESS EXISTING WITH NO
 UPGRADES.
  
 6) STANDPIPES CONNECTIONS SHALL BE 2
 1/2"- 1 1/2" REDUCER WITH CHAINS.
  
 7) FIRE SPRINKLERS APPEAR TO BE MISSING
 AT STAIRWAY #1. SHT FS2.5.
  
 8) PLEASE SHOW LOCATION OF FIRE
 DEPARTMENT CONNECTION.
  
 9) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 10) NOTE #18 ON SHT FA0.1 SHOULD READ
 FIRE ALARM SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 11) SMOKE DETECTOR IS REQUIRED IN AREA
 OF FACP.
  
 12) KNOX BOX IS REQUIRED IF NOT ALREADY
 PROVIDED NEAR FRONT DOOR.
  
 13) THIS PROJECT WOULLD APPEAR TO MEET
 THE DEFINITION OF MIXED OCCUPANCY AND
 THEREBY SHALL COMPLY WITH NFPA 101,
 SECTION 6.1.14.3.
  
 14) PLEASE PROVIDE A LIFE SAFETY PLAN
 THAT ILLUSTRATES MAXIMUM TRAVEL
 DISTANCES.
  
 15) PLEASE PROVIDE NOTE ON ELEVATIONS
 INDICATING THAT ADDRESS SHALL BE AT
 LEAST 6" IN HEIGHT AND CONTRASTING TO
 THE BACKGROUND.
  
 16) STAIRS TO COMPLY WITH APPLICABLE
 BUILDING CODES AND NFPA 101, 2003
 EDITION SECTION 7.2.2.2.1(A)
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  