Plan Review Notes
Plan Review Notes For Permit 06070917
Permit Number 06070917
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-07 00:00:00REVIEW IN PROGRESS
 *** UNSAT ***
  
 1) NOTE: PLEASE HAVE PLANS REFERENCE THE
 FOLLOWING SPECIFIC CODES.
 2002 NFPA-70, 2002 NFPA-72 AND 2003
 NFPA-101.
 PLANS SHOULD ALREADY REFLECT THE 2004
 FBC.
  
 2) NOTE: PLEASE SEE MISSING LIGHTING
 REQUIRD FOR MECH RM. 210.70.
  
 3) NOTE: PLEASE SEE 110.26 AS MIN
 CLEARENCES FOR DISCONNECTS IN ELEV
 EQUIPMENT RM DO NOT SEEM TO MEET 110.26
 PLEASE SEE ALSO PLASN ARE SHOWING AN AHU
 IN ELEVATOR EQUIPMENT ROOM. PLEASE SEE
 STATE ELEVATOR CODE FOR EQUIPMENT OTHER
 THAN ELEVATOR EQUIPMENT PERMITTED IN THE
 ELEV EQUIPMENT ROOM.
  
 4) NOTE: PLEASE CLARIFY ELEVATOR LOBBY
 DOES NOT SEEM TO INDICATE AN EM BACK UP
 LIGHTING FOR EGRESS.
 LS 101 7.8,7.9
  
 5) NOTE: PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR STAIR-TOWERS. PLEASE
 SEE UNDER THE 2003 LS 101 7.8.1.3,
 REQUIRES A MIN OF 10FT CANDLES ON NORMAL
 AND IS PERMITTED DOWN TO 1FT CANDLE
 UNDER EM POWER.
 IF BOTH STAIRS ARE THE SAME , A TYPICAL
 DETAIL MAY BE SHOWN.
  
 6) NOTE: PLEASE SEE PLANS ARE SHOWING
 PANELS ON EACH FLR , HOWEVER PLEASE SEE
 THESE ARE NOT IDENTIFIED OR ON
 ELECTRICAL RISER. IF THESE ARE "FUTURE"
 PLEASE INDICATE OR NOTE AS FUTURE>
 IF THESE ARE GOING TO BE INSTALLED AT
 THIS TIME, PLEASE LABEL AND COMPLETE
 RISER.
 106.1.2 FBC
  
 7) NOTE: PLEASE SEE FBC 2004 CHAPTER 13
 FOR MIN LIGHTING CONTROLS REQUIRED FOR
 EACH FLR. PLEASE SEE EACH DEVICE SHOULD
 BE NOTED FOR TIME OF OVER RIDE ETC
 THE LIGHTING MUST BE ABLVE TO BE
 OVERRIDIN WHERE EGRESS INTO SPACE IS
 LOCATED.
 30MINS MAX FOR OCCUPANCY SENSORS TYPES,A
 ND 4 HRS MAX FOR TIMER TYPES.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2,
 .1.3
  
 8) NOTE: PLEASE VERIFY THE HEIGHT
 REQUIRED ON RISER AS THIS AREA BEHIND
 BUILDING (EAST ELEV) MAY BE SUBJECT TO
 VEHICULAR TRAFFICE WHICH WOULD REQUIRE
 RISER TO BE INSTALL HIGH ON EAST WALL.
 THIS IS BROUGHT UP AT THIS TIME AS THE
 MINIMUM CLEARENCES FROM WINDOW OPENINGS
 WILL NEED TO BE CHECKED FOR MIN CLEARENCES.230.24B,
 230.9
  
 9) NOTE: PLEASE SEE PLANS DO NOT
 INDICATE RISER ON THE OUTSIDE OF THE
 BUILDING FOR HOUSE SERVICE. PLEASE ALSO
 KNOW, THE HOUSE SERVICE MAY NOT BE
 LOCATED INSIDE ANY TENANT SPACE OR
 FUTURE TENANT SPACE. PLEASE SEE MAINS
 SHALL BE GROUPED ETC.
 210.25, 230.72,
  
 10) NOTE: PLEASE SEE PLANS NOTE TO
 CONNECT NEW SERVICE GROUNDING ELECTRODE
 CONDUCTOR TO FOOTER STEEL. PLEASE KNOW
 IF THIS WERE A NEW BUILDING, THIS WOULD
 CERTAINLY BE REQUIRED, HOWEVER PLEASE
 KNOW AS THIS BUILDING IS VERY OLD IT MAY
 NOT EVEN CONTAIN STRUCTURAL FOOTER
 STEEL. PLEASE KNOW, CONNECTION TO THE
 FOOTER STEEL WOULD JEOPARDIZE THE
 STRUCTURAL INTEGRITY OF THE EXISITING
 BUILDING AND THERFORE IT IS NOT
 RECOMMENDED, HOWEVER MAY BE DONE. IF
 SHOWN ON PLANS, THIS WILL BE REQUIRED.
 PLEASE KNOW, IF NOT, PLEASE PROVIDE A
 MIN OF 2-GRND RODS.
 250.50,250.56 ETC
  
 11) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%. 215.3,230.42 ETC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW