Plan Review Notes
Plan Review Notes For Permit 06070858
Permit Number 06070858
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-20 00:00:00*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SHOW ALL NEW/EXISTING
 CIRCUTING ON PLANS FOR LTS, APPLIANCES
 ETC AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE PANEL SCHEDULES NOW SHOW ALL
 THE NEW CIRCUITS, YET THESE ARE NOT ON
 PLANS.
  
 2) NOTE: PLEASE SEE A "PRIVATE PROVIDER'
 AFFIDAVIT IS BEING SUBMITTED STATING
 ELECTRICAL PLANS REVIEWED FOR CODE
 COMPLIANCE BY MR. ERIC WOODS FOR PLANS
 DATED 6/12/06 AND 7/11/06. PLEASE SEE
 NEW PLANS SUBMITTED WHICH WERE REVISED
 BY THE ARCHITECT IS DATED 8/3/06.
 PLEASE SEE ONLY ONE AFFIDAVIT WAS
 SUBMITTED ON ONE COPY OF THE ELECTRICAL
 PLANS FOR THIS.
 PLEASE SEE THE OTHER TWO SETS OF PLANS
 CONTAIN AFFIDAVIT WHICH STATS
 ARCHITECTURAL PLANS DATED 6/16/06 AND
 7/11/06 REVIEWED FOR CODE COMPLIANCE ,
 YET THESE WERE ALSO REVISED WITH NEW
 SHEETS DATED 8/3/06
 IF CONTRACTOR IS GOING TO SUBMIT PLANS
 DONE BY A "PRIVATE PROVIDER" THEN, ALL
 REVISED PLANS MUST GO BACK TO SAID
 PROVDER FOR REVIEW ETC.
 PLEASE ALSO SEE THE PLANS WERE ALSO NOT
 STAMPED BY THE "PROVIDE PROVIDER"
 COMPANY AS DONE ON THE PREVIOUS PLANS,
 "REVIEWED FOR CODE COMPLIANCE".
 PLEASE SEE THE AFFIDAVIT(S) ARE LISTING
 TWO DIFFERENT PERSONS PROVIDING
 SERVICES. PREVIOUS AFFIDAVIT ALSO LISTED
 TWO DIFFERENT PERSONS. THESE AFFIDAVITS
 ARE NOTARIZEDUNDER FS 117.05 AS BEING
 TAKEN UNDER OATHETC.
 THIS AFFIDAVIT IS NOT VALID BASED ON
 STATEMENTS, PLANS, ETC.
 FS 553.79(1).
 ** PLEASE KNOW , ONE SET OF EACH OF THE
 OLD PLANS AND NEW PLANS SUBMITTED ARE
 BEIGN RETAINED BY THIS OFFICE.
  
  
 ** PLEASE KNOW, THE PLANS COULD BE
 STAMPED AND PASSED WITH A "PROVISO" FOR
 ELECTRICAL AND ISSUANCE, HOWEVER SINCE
 PLANS ARE BEING SUBMITTED BY THE
 CONTRACTOR FOR "PRIVATE PROVIDER NOTE #2
 MUST BE ADDRESSED.
  
 ** PLEASE CALL TO GO OVER ANY QUESTIONS,
 OR OPTIONS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]