| 2006-07-23 00:00:00 | ****UNSAT **** |
| | |
| | 1) NOTE: PLEASE PROVIDE CIRCUITING FOR |
| | NEW ELECTRICAL DEVICES ON PLANS. PLEASE |
| | LABEL THE APPLIANCES BEING LISTED IN |
| | LOAD CALCULATIONS. |
| | PLEASE LIST THE NEW CIRCUIT(S) INCLUDING |
| | THE DEDICATED BATH(S) RECEPTS AS NOTED |
| | 210.11C3, MUST BE 20A AND #12. |
| | PLEASE PROVIDE A PANEL SCHEDULE FOR NEW |
| | CIRCUITINGAND EXISTING. PLEASE LIST |
| | THE OCP AND CONDUCTOR SIZES FOR NEW |
| | CIRCUITS AND /OR EIXSITNG CIRCUITS WHICH |
| | MAY BE UTILIZED. |
| | 240.4,310.16,408.4 |
| | 106.1.2 FBC ADMIN SECT AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SEE NEC 2002 IS BEING |
| | REFERENCED FOR REQUIREMENTS OF SMOKE |
| | DETECTORS IN NOTES, WHERE REQUIREMENTS |
| | ARE FROM NFPA-72. THE CURRENT CODE IN |
| | EFFECT IS 2002. 11.5.1.1, 11.8.3 |
| | |
| | 3) NOTE: PLEASE SEE NOTE FOR CLOSET LT |
| | MENTIONS SHALL BE OFFSET 6" MINIMUM FROM |
| | SHELVING, HOWEVER DEPENDING ON FIXTURE |
| | TYPE, THIS MAY INDEED BE REQUIRED AT |
| | 12". PLEASE LIST PROPOSED FIXTURE AND |
| | SEE 410.8 FOR REQUIRED FIXTURE TYPES AT |
| | 6". |
| | |
| | 4) NOTE: PLEASE SEE THE PROVIDE PROVIDER |
| | NOTICE TO BUIDLINF OFFICAL DOES NOT |
| | INDICATE IF THIS WILL BE FOR PLAN REVIEW |
| | OR INSPECTIONS OR BOTH. PLEASE KNOW, |
| | THESE ARE REQUIRED TO BE INDICATED. |
| | PLEASE ALSOTHREE DIFFERENT "PROVIDE |
| | PROVIDERS" ARE LISTED IN PAPERWORK AND |
| | ONLY ON SIGNIGN AN AFFIDAVIT. PLEASE SEE |
| | TWO SEPARATE NAME LISTED ON AFFIDAVIT. |
| | PLEASE CORRELATE AND ADJUST. |
| | |
| | ** ONLY A NOTE** |
| | PLEASE VERIFY THE LOADS SHOWN FOR WATER |
| | HEATER AS THIS IS NOT A STANDARD HEATING |
| | ELEMENT SIZE. |
| | PLEASE ALSO SEE THE LOADS SHOWN FOR |
| | DOUBLE OVENS AND COOKTOP BOTH SEEM VERY |
| | LOW. THIS IS A NOTE TO VERIFY AND ADJUST |
| | AS NEEDED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |