| 2007-03-07 18:08:29 | DENIED |
| | REFERNCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | FROM PREVIOUS REVIEWS |
| | |
| | A. OK |
| | B. OK |
| | |
| | C.THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR REVIEW FOR GAS PERMIT: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. N/A |
| | 7. OK |
| | 8.N/A |
| | 9. OK |
| | |
| | ************NEW COMMENTS************* |
| | |
| | A. NEW PLANS WITH NEW INFORMATION REQUIRE NEW COMMENTS. |
| | NOW LP-GAS ALSO INDICATED ON PLANS. |
| | |
| | 1B. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - THE LENGTHS OF PIPE SHOWN ON THE |
| | ISOMETRIC DO NOT REFLECT THE LENGTHS OF PIPE AS SCALED |
| | ON THE 1/8" SCALE FLOOR PLAN.SCALE INDICATES THE |
| | TOTAL DEVELOPED LENGTH ON THE NATURAL GAS SYSTEM TO BE |
| | APPROX. 131'. PLEASE CLARIFY. SECTION 106.1.1.-- SHOW |
| | THE SHUT OFF VALVE UPSTREAM OF THE REGULATORS. SECTION |
| | 409.4. A DRIP/SEDIMENT TRAP IS REQUIRED DOWNSTREAM OF |
| | THE EQUIPMENT SHUT OFF VALVE. SECTIONS 408.2 & 408.4. |
| | |
| | 2B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - AS INDICATED IN COMMENT |
| | 1B. THE TOTAL DEVELOPED LENGTH APPEARS TO BE ABOUT |
| | 131'. PLEASE VERIFY. SECTION 106.1.1. |
| | |
| | 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | SECOND STAGE REGULATORS FOR THE NATURAL GAS AND LP GAS |
| | SYSTEMS. THE REGULATORS SHALL BE LISTED AND INDICATE |
| | THE MODEL NUMBER FOR EACH REGULATOR ON MANUF. |
| | SPECIFICATION SHEETS. SECTION 410.2((2)(3). |
| | |
| | 4B. SUBMIT THE MANUF. SPECIFICATIONS FOR THE "AUTOMATIC |
| | TRANSFER SOLENOID SWITCH" INDICATED ON THE STANDBY |
| | GENERATOR MECHANICAL PLAN. THIS SOLENOID TRANSFER |
| | SWITCH SHALL BE LISTED FOR BOTH NATURAL GAS AND LP GAS |
| | AND SHALL INDICATE INSTALLATION INSTRUCTIONS. SECTION |
| | 106.1.2. |
| | |
| | 5B. SHOW THE PIPE SIZE OF THE EXISTING NATURAL GAS LINE |
| | FROM THE NATURAL GAS METER TO THE POINT OF CONNECTION |
| | OF THE NEW PE PIPE. ALSO INDICATE THE MATERIAL OF THAT |
| | EXISTING PIPE. SECTION 106.1.2 AND TABLES 402.4. |
| | |