| 2007-02-25 10:20:27 | *** UNSAT 2NDREVIEW *** |
| | |
| | |
| | ** THE *RESUB* FEE WAS NOT PAID WHEN PLANS WERE |
| | RESUBMITTED WHICH IS REQUIRED. PLANS WILL NOT BE |
| | RELEASED UNTIL FEE IS PAID. |
| | |
| | ** ONE COPY OF PLANS AND COPY OF PERMIT APPLICATION |
| | WILL BE RETAINED BY THIS OFFICE. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | PERMIT WAS APPLIED FOR BEFORE THE CODES CHNAGES OF |
| | DECEMBER 8TH, 2006. |
| | 2004 FBC. |
| | 2002 NFPA-70 (NEC). |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE |
| | REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR |
| | REVIEWER(S). |
| | PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH |
| | REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD |
| | BE REVISED ACCORDINGLY. |
| | |
| | 2) NOTE: PLEASE SEE GAS REVIEW NOTES, AS NO |
| | MANUFACTURES/SPECS CUTS SHEETS WERE SUBMITTED FOR TANK |
| | AS PROPOSED. |
| | GAS PERMIT IS APPLIED FOR AT THIS TIME AND PLANS |
| | INDICATE UNDER SEPARATE PERMIT? |
| | PLEASE SEE GAS REVIEW NOTES. |
| | |
| | 3) NOTE: PLEASE SEE MANUFACTURES SPECS/CUT SHEETS WHICH |
| | REFLECT A 700AMP BREAKER FEEDING A 600A PANEL WHERE |
| | PLANS CALL FOR A 600AMP BREAKER AT THIS SAME LOCATION |
| | FOR THE GENERATOR? PLEASE CORRELATE AND ADJUST AS |
| | NEEDED. |
| | |
| | 4) NOTE: PLEASE SEE NOTE #3 ABOVE WITH RESPECT TO |
| | CONDUCTOR SIZES IF INDEED THE BREAKER IS 700AMPS? |
| | 310.16, 240.4 |
| | |
| | 5) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS TO PLACE |
| | NEW CIRCUITS INTO PANEL *EM* WHICH ARE NOT LEGALLY |
| | REQUIRED OR EMERGENCY SYSTEMS REQUIRED CIRCUITS. PLEASE |
| | SEE THE NEC 700 AND 701 AS 702 TYPE CIRCUITS MAY NOT BE |
| | IN SAME EQUIPMENT. |
| | PLEASE DO NOT INDICATE SYSTEMS OTHER THAN MENTIONED |
| | ABOVE UNLESS INSTALLING ANOTHER 702 SYSTEM WHICH WILL |
| | REQUIRE A SEPARATE ATS AND LOAD SHEDDING, PANEL |
| | SCHEDULE, LOADS ETC. |
| | PLEASE SEE THE LOAD SUMMARY ON PLANS DOES NOT INCLUDE |
| | ANY OF THESE LOADS MENTIONED IN NOTES. |
| | PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR THE |
| | EXISTING EM PANEL. |
| | 310.16, 240.4, 215.5, 701.6, 700.6, 702.6, 408.4, ETC |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | PLEASE ALSO SEE CHAPTER 6 OF NFPA-110 2002. |
| | |
| | 6) NOTE: PLEASE SEE AS STATED IN PREVIOUS REVIEW; |
| | PLEASE SUBMIT ALL PLANS INTO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. PLEASE DO NOT SUBMIT LOOSE SHEETS. PLEASE |
| | BE SURE TO REMOVE ANY OLD/VOIDED SHEETS FROM SHEETS. |
| | |
| | 7) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE FLOOD |
| | ELEVATION AS REQUIRED PER CHAPTER 7 OF NFPA-110. PLEASE |
| | STATE IF THIS ELEVATION IS THAT FROM TEH SLOSH CHARTS |
| | BASED ON A CAT 4 HURRICANE OR THAT OF THE LEVELS BASED |
| | ON THE " 100 YR STORM LEVEL". |
| | 7.2.3* |
| | |
| | 8) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE |
| | SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND |
| | MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT |
| | IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED |
| | BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT |
| | GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS |
| | NOTED ABOVE. |
| | AS THE SCOPE OF WORK HAS ONCE AGAIN INCREASED THE VALUE |
| | HAS NOT BEEN ADJUSTED, PLEASE DO SO OR A VALUE WILL BE |
| | ASSESSED USING THE FBC AND MARSHALL'S & SWIFT GUIDES. |
| | |
| | 9) NOTE: THE TIME FOR FUEL CONSUMPTION SHALL BE PLACED |
| | ON PLANS BASED ON THE "ON-SITE" FUEL. |
| | THIS WAS NOTED ON PREVIOUS REVIEW. |
| | |
| | ** PLEASE KNOW BASED ON THE ELECTRICAL RISER SUBMITTED |
| | OF THE EXISTING ELECTRICAL SERVICE, THERE ARE SEVERAL |
| | ITEMS WHICH ARE NOT COMPLIANT FOR THE CURRENT CODES AND |
| | CODES FOR AT LEAST THE LAST 20 YEARS, THIS REVIEWER IS |
| | NOT RESPONSIBLE FOR THE EXISTING ELECTRICAL SERVICE AND |
| | HOW EQUIPMENT IS FED. NO SCOPE OF WORK IS BEING APPLIED |
| | FOR TO UPDATE OR DO WORK WITH THE EXISTING SERVICE AS |
| | SHOWN. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |