| Date |
Text |
| 2006-08-02 00:00:00 | ************ UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE PLANS SUBMITTED AR |
| | PHOTO-COPIES OF SIGNEDAND SEALED |
| | PLANS. |
| | PLEASE SEE FS 471.025, FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE PLANS NOTE THAT THE |
| | GEN IS NOT REQUIRED FOR LIFE SAFETY: |
| | PLEASE PROVIDE INFORMATION FOR WHAT IS |
| | PROVIDING BACK UP FOR EM SYSTEMS. |
| | CAN NOT VERIFY CODE COMPLIANCE ITEMS AT |
| | THIS TIME FOR THIS. |
| | IS THIS BUIDLING A HIGH-RISE? |
| | PLEASE SEE 700.12B3 |
| | PLEASE SEE 701.11B3 |
| | PLEASE SEE THAT NO PANEL SCHEDULES, |
| | INTENDED LOADS ETC WERE SUBMITTED OR |
| | SHOWN FOR THIS NEW GENERATOR. |
| | |
| | 3) NOTE: PLEASE PROVIDE AN ELECTRICAL |
| | DIAGRAM TO VERIFY CONDUCTORS, FEEDERS, |
| | CONDUITS, OCP ETC ETC. |
| | PLEASE SEE NO INFORMATION OR ELECTRICAL |
| | PLANS WERE SUBMITTED SHOWING HOW THIS |
| | UNIT IS BEING WIRED IN WITH THE EXISTING |
| | SERVICE. |
| | PLEASE PROVIDE OCP ON GENERATOR ETC. |
| | PLEASE PROVIDE AIC RATINGS ETC |
| | PLEASE SEE NEC 2002. |
| | THERE ARE TOO MANY CODE ARTICLES TO |
| | REFERENCE TO COMPLETE PLANS. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR NEW GEN, WP |
| | ENCLOUSURE (IF NOT PART OF GEN) ETC. |
| | 106.1.2, NEC 90.8, 110.3 ETC |
| | |
| | ** PLEASE KNOW, PLANS AND SUBMITTED |
| | PACKAGE IS NOT COMPLETE AT THIS TIME AND |
| | THERE MAY BE FURTHER COMMENTS ONCE PLANS |
| | ARE COMPLETE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |