Plan Review Notes
Plan Review Notes For Permit 06070811
Permit Number 06070811
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-09 00:00:00*** UNSAT **
  
 1) NOTE: PLEASE SEE AT THIS TIME CAN NOT
 VERIFY GROUPING OF MAINS. PER 230.72,
 AND 225.34.
 PLEASE CLARIFY IF THE MDP CONTAINS A
 MCB?, THEN ALL MAINS ARE NOT GROUPED. IT
 SEEMS WHICH IF YOU WERE INSIDE AND MDP
 CONTAINED NO MAIN, THEN NEW MAIN FOR THE
 MDP FOR POSSIBLE GENERATOR FEEDERS IS
 OUTSIDE AND WOULD NOT GROUPED WITH OTHER
 MAINS. (HOUSE MAIN, AND MAIN FOR
 SERIVICE.
 PLEASE ALSO SEE GUTTER IS BEING SHOWN
 BELOW EXISTING MAIN WHICH MUST MEET
 110.26. PLEASE VEIRFY THE DEPT OF THE
 MAIN AND THE DEPTH OF THE GUTTER, AS
 GUTTER MAY NOT EXTEN MORE THAN 6" OUT.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  