| 2006-07-16 00:00:00 | ************ UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE PERMIT APPLICATION |
| | MUST CONTAIN AN ORIGINAL SIGNATURE FOR |
| | QUALIFIER/OR AUTHORIZED AGENT. PLEASE |
| | SEE APPLICATION IS A COLORED PHOTO-COPY |
| | OF THE CONTRACTORS SIGNATURE. PLEASE |
| | ALSO SEE THIS APPLICATION WAS NOTORIZED |
| | IN VIOLATION OF FS 117.05, AS A NOTORY |
| | MAY NOT UNDER ANY CIRCUMSTANCES NOTORIZE |
| | A "PHOTO-COPIED" SIGNATURE. |
| | APPLICATION IS BEING RETAINED AND TURNED |
| | OVER TO THE PERMIT/LICENSING MANAGER. |
| | |
| | 2) NOTE: PLEASE SEE THAT THE |
| | PLANS/RISER/DRAWING SUBMITTED MUST |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR |
| | PLANS/DESIGN. THIS IS NOT REQUIRED TO BE |
| | NOTORIZED, HOWEVER IF IT IS, PLEASE BE |
| | SURE ALL INFORMATION IS PROVIDED FOR IT |
| | TO BE LEGALLY NOTORIZED. FS 117.05 |
| | |
| | 3) NOTE: PLEASE SUBMIT MANUFCATURE |
| | SPECS/CUT SHEETS FOR THE NEW PROPOSED |
| | MTS. |
| | PLEASE SEE THAT THE MTS WILL NOT BE |
| | PERMITTED AS SHOWN ON RISER. IF THE |
| | INTENTION TO TO PROVIDE CONNECTIONS FOR |
| | POSSIBLE FUTURE PORTABLE GENERATOR, THEN |
| | PLEASE MAKE THE CORRECT |
| | JUNCTION/CONNECTION FOR THIS. AS SHOWN, |
| | THIS WOULD PLACE THE FEEDERS INTO THE |
| | SAME GUTTER WITH THE LOAD SIDE OF THE |
| | MTS. PLEASE CLARIFY INSTALLATION. |
| | 110.3,702.6,ETC. |
| | |
| | 4) NOTE: PLEASE PROVIDE A SIGNED |
| | CONTRACT AS VALUE SEEMS LOW FOR PROPOSED |
| | SCOPE OF WORK. ALL LABOR AND MATERIALS |
| | SHALL BE INCLUDED EVEN IF ANY IS OWNER |
| | SUPPLIED. |
| | FCB 108.3 ADMIN SECT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |