Plan Review Notes
Plan Review Notes For Permit 06070806
Permit Number 06070806
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-08 00:00:00***** UNSAT *****
  
 ** PLEASE SEE MANY ITEMS BELOW ARE NEW
 COMMENTS AS MANY ITEMS ON PLANS ARE
 BEING SUBMITTED FOR THE FIRST TIME.
  
 1) NOTE: PLEASE SUBMIT THE LETTERS FROM
 THE ARCHITECT AND ENGINEERS FOR PROJECT
 AS ORIGINAL. PLEASE KNOW THE LETTERS
 FROM THE ORIGINAL ARCHITECT SHALL BE
 ORIGINAL SIGNED, DATED AND SEALED.
 PLEASE SEE LETTERS ATTACHED TO PLANS ARE
 PHOTO-COPIES AND NONE ARE DATED AND
 SEALED.
 PLEASE SEE ONLY ONE LETTER FROM THE
 ENGINEERING FIRM CONTAINS AN ORIGNAL
 SIGNATURE. OTHER TWO LETTERS ARE ALSO
 PHOTO-COPIESAND NO LETTERS ARE SEALED
 WITH RAISED SEAL O R DATED.
 PLEASE SEE NO LETTER FROM THE NEW
 ARCHITECT RECORD TAKING RESPONSIBILTY
 FOR NEW PLANS / DESIGN AND PROJECT COULD
 BE LCATED ON PLANS OR IN SAID PACKAGE.
  
 ** PLEASE KNOW, ALL LETTERS WHICH ARE
 SIGNED, DATED AND SEALED IN FLORIDA,
 SHALL BE CORRECTLY NOTARIZED AS REQUIRED
 UNDER FS 117.05 WITH ALL INFORMATION AS
 REQUIRED BE NOTARY.
 PLEASE SEE FS 481 AND 471 FOR
 REQUIREMENTS OF NEW DESIGNERS TAKING OVE
 OF PROJECT(S).
  
 2) NOTE: PLEASE SEE 210.52B1, AS DINING
 ROOM AND AREAS OF THE LIKE SHALL BE ON
 ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE KNOW, EACH CIRCUIT OVER
 THE TWO MIN, SHALL ALSO BE FIGURED AT
 THE MIN 1500VA EACH. PLEASE SEE DINGIN
 IS SHOWN AS 540 AND OTHER APPLIANCE
 CIRCUITS ARE SHOWN AS 1200VA.
 NOTE**PLEASE VERIFY REFRIGERATOR, IF
 LOAD OF FRIG IS OVER 750VA , THEN A
 DEDICATED CIRCUIT IS REQUIRED.THIS IS
 ONLY NOTED.
 PLEASE SEE 210.52B1, 210.11C1,220.16
  
 3) NOTE: PLEASE SEE 220.18 AS LOAD TO BE
 FIGURED FOR DRYER SHALL BE 5KW MIN.
 PLEASE ALSO ADJUST THE BRANCH CIRCUIT
 FOR MIN OF #10 AWG AND 30A OCP.
 240.4,310.16
 PLEASE SEE PLANS ALSO INDICATE THIS AS A
 "STACKABLE UNIT" AND NOT SEPARATE UNITS.
  
 ** THERE IS NOT ENOUGH CLEARNECE FOR
 TWO UNITS AS ALL AUTOMATED PANELS ETC
 ARE IN SAME AREA.
  
 4) NOTE: PLEASE INDICATE CIRCUITING ON
 PLANS FOR ALL. PLEASE SEE SD'S.
 408.4,
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS REQUIRED FOR ALL OUTLETS IN BEDRMS OR
 ADAPTABLE SLEEPING ROOMS.
 2002 NEC, 210.12, THIS INCLUDES SD'S,
 LTS, RECEPTS ETC.
 PLEASE SEE THIS INCLUDES THE "STUDY"
 WHICH IS AN ADAPTABLE SLEEPING ROOM.
  
 6) NOTE: PLEASE SEE WASHER IS BEING
 SHOWN A 220V UNIT ON PANEL SCHEDULE WITH
 A 3KW LOAD? PLEASE CORRELATE AS THE
 WASHER ON LOAD CALCULATIONS ONLY
 INDICATE THIS AS A 1500VA , 120V UNIT??
 210.11C2, 220.16B.
  
 7) NOTE: PLEASE SEE ELECTRICAL PLANS DO
 NOT INDICATE OR SHOW ANY ELECTRICAL FOR
 CABANA REMODEL. PLEASE SEE MISSIGN ITEMS
 ON PANEL SCHEDULES, DEDICATED CIRCUITS
 ETC.
 ARCHITECTURAL PLANS DO INDICATE THIS
 BEING IN SCOPE OF WORK.
  
 8) NOTE: PLEASE BE SURE SUITE/ UNIT
 NUMBER IS LOCATED ON THE TITLE BLOCKS ON
 ALL SHEETS AS REQUIRED PER FAC
 61G1-16.004 AND 61G15-23.002
 ** THIS CAN BE HAND WRITTEN ON TITLE
 BLOCKS WHICH ALREADY CONTAIN STAMPS FOR
 THE REVIEWS WHICH HAVE PASSED.
  
 9) NOTE: PLEASE KNOW, ALL PLANS/SETS AND
 ALL SHEETS SHALL CONTAIN THE CODES
 CURRENTLY UNDER ADOPTION UNDER FS'S 553
 AND FBC 2004 WHICH ARE RELEVANT TO PLANS
 AND DEISGNS SUBMITTED.
 PLEASE SEE 2004 FBC, 2002 NFPA-70 (NEC),
 2002 NFPA-72 IS REQUIRED AT A MIN,
 INLCUDING 2004 FBC FOR MECH AND PLUMB.
 THIS IS REQUIRED ON SHEETS WHETHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 10) NOTE: PLEASE REMOVE ELECTRICAL PLANS
 DONE BY ARCHITECTURAL FIRM, AS THE
 REVISED PLANS DONE BY THE ENGINEERING
 FIRM SEEMS TO BE THE ONES SUBMITTED FOR
 SCOPE PF WORK.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  