| 2006-07-24 00:00:00 | ******* UNSAT ********** |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETE |
| | ELECTRICAL PLANS FOR REVIEW. PLEASE |
| | INCLUDE NEW LIGHTING CONTROL SYSTEM |
| | WHICH IT IS KNOWN TO THIS OFFICE. |
| | PLEASE SUBMIT SPECIFICATIONS ON SYSTEM. |
| | PLEASE SEE 2002 NFPA-72 AND 2002 NFPA-70 |
| | PLEASE PROVIDE CIRCUITING AND CORRELATE |
| | WITH PANEL SCHEDULES TO BE SUBMITTED. |
| | PLEASE LIST ALL THE REQUIRED CIRUCITS |
| | ALONG WITH OCP AND AWG SIZES FOR ALL. |
| | |
| | 215.5,240.4,310.16,220.16,220.31, |
| | 210.52, 210.5211C, 210.8A ETC |
| | |
| | 2) NOTE: PLEASE CLARIFY TITLE BLOCK AS |
| | IT LISTE MPERRY DESIGN INC/ AMES BENNET |
| | PA.IF THIS IS A NEW FIRM PLEASE |
| | PROVIDE CERTIFICATE OF AUTHORIZATION |
| | NUMBER AS REQUIRED PER FS 481.219 OR |
| | PLEASE ADJUST TITLE BLOCKS. |
| | PLEASE ALSO CLARIFY BRUCE BEIRMAN DESIGN |
| | INC ALSO FOR REQUIRED LICENSURE. FS |
| | 481.219, FAC 61G1-16.004. |
| | PLEASE KNOW, ALL FIRMS LISTED ON TITE |
| | BLOCKS SHALL CONTAIN ALL REQUIRED |
| | INFORMATION. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE THE ELECTRICAL |
| | SPECIFICATION SHEETS WERE STAMPED IN |
| | ERROR FROM MECHANICAL REVIEWER AND HAVE |
| | BEEN VOIDED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |