Text |
| 2006-07-18 00:00:00 | ***** UNSAT ***** |
| | |
| | ** PLEASE KNOW, PLANS WERE RE-REVIEWED |
| | AS DESIGN TEAM CALLED AND SAID |
| | INFORMATION WAS ON PLANS. |
| | |
| | ** PLEASE KNOW, ELECTRICAL NOTES PLACED |
| | ON REVIEW DONE BY MR BILL TROBAUGH STILL |
| | STAND. PLEASE SEE NOTES AS FOLLOWS FOR |
| | ANY ELECTRICAL CLARIFICATION AND ALSO |
| | NEW NOTES DUE TO THIS PLAN REVIEWERS |
| | OBSERVATION/REVIEW. |
| | |
| | 1) NOTE: PLEASEPROVIDE LOCATION OF ALL |
| | LTS POLES ON PLANS. |
| | PLEASE INDICATE THE CONDUIT SIZES, ALONG |
| | WITH CONDUCTOR SIZES AND TYPES BEING |
| | INSTALLED. |
| | PLEASE INDICATE THE FPL TRANSFORMER |
| | LOCATION ON PLANS IN WHICH THESE ARE |
| | BEING CONNECTED. THIS OFFICE IS AWARE OF |
| | THE "INLINE" FUSES AND HOW THE BILLING |
| | IS DONE FOR CITY LIGHT POLES. PLEASE |
| | ONLY INDICATE THE OCP FOR THE "INLINE " |
| | FUSES AND VOLTAGE BEING CONNECTED. |
| | FBC ADMIN SECT 106.1.2, NEC |
| | 240.4,310.16, ETC |
| | |
| | 2) NOTE: PLEASE SEE PLANS ARE NOT |
| | SIGNED,DATED OR SEALED BY THE DESIGN |
| | PROFESSIONAL ON SAID TITLE BLOCKS. |
| | PLEASE DO SO. FS 471.025 |
| | |
| | 3) NOTE: PLEASE SEE WIND LOAD |
| | CALCUALTIONS WHICH CONTAINED A RAISED |
| | SEAL OF A SIGNATURE AND DATE WHICH IS |
| | NOT ORIGINAL AND IS INDEED A |
| | "PHOTO-COPY" OF SIGNED SHEETS. |
| | PLEASE SEE FAC 61G15-23.002, FS 471.025 |
| | AS THE SIGNATURE AND DATE SHALL BE |
| | ORIGINAL WITH RAISED SEAL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |