Plan Review Notes
Plan Review Notes For Permit 06070786
Permit Number 06070786
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-18 00:00:00***** UNSAT *****
  
 ** PLEASE KNOW, PLANS WERE RE-REVIEWED
 AS DESIGN TEAM CALLED AND SAID
 INFORMATION WAS ON PLANS.
  
 ** PLEASE KNOW, ELECTRICAL NOTES PLACED
 ON REVIEW DONE BY MR BILL TROBAUGH STILL
 STAND. PLEASE SEE NOTES AS FOLLOWS FOR
 ANY ELECTRICAL CLARIFICATION AND ALSO
 NEW NOTES DUE TO THIS PLAN REVIEWERS
 OBSERVATION/REVIEW.
  
 1) NOTE: PLEASEPROVIDE LOCATION OF ALL
 LTS POLES ON PLANS.
 PLEASE INDICATE THE CONDUIT SIZES, ALONG
 WITH CONDUCTOR SIZES AND TYPES BEING
 INSTALLED.
 PLEASE INDICATE THE FPL TRANSFORMER
 LOCATION ON PLANS IN WHICH THESE ARE
 BEING CONNECTED. THIS OFFICE IS AWARE OF
 THE "INLINE" FUSES AND HOW THE BILLING
 IS DONE FOR CITY LIGHT POLES. PLEASE
 ONLY INDICATE THE OCP FOR THE "INLINE "
 FUSES AND VOLTAGE BEING CONNECTED.
 FBC ADMIN SECT 106.1.2, NEC
 240.4,310.16, ETC
  
 2) NOTE: PLEASE SEE PLANS ARE NOT
 SIGNED,DATED OR SEALED BY THE DESIGN
 PROFESSIONAL ON SAID TITLE BLOCKS.
 PLEASE DO SO. FS 471.025
  
 3) NOTE: PLEASE SEE WIND LOAD
 CALCUALTIONS WHICH CONTAINED A RAISED
 SEAL OF A SIGNATURE AND DATE WHICH IS
 NOT ORIGINAL AND IS INDEED A
 "PHOTO-COPY" OF SIGNED SHEETS.
 PLEASE SEE FAC 61G15-23.002, FS 471.025
 AS THE SIGNATURE AND DATE SHALL BE
 ORIGINAL WITH RAISED SEAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  