| Plan Review Notes For Permit 06070735 |
| Permit Number |
06070735 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-11 00:00:00 | *****APPROVED*****W/PROVISO | | | | | | | | | | | | | | | 1.) STRUCTURES UNDERGOING CONSTRUCTION, | | | ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241. | | | | | | 2.) THE STORAGE OR DISPOSAL OF ROOFING | | | AND(OR) BUILDING MATERIALS/WASTE SHALL | | | NOT INTERFERE OR HINDER EMERGENCY | | | RESPONDERS ACCESS TO THE STRUCTURE. | | | | | | 3.) VERIFY THAT A NUMERICAL ADDRESS OF | | | NO LESS THAN 6" IN HEIGHT AND 1" IN | | | WIDTH IS POSTED ON THE BUILDING. | | | SUITES/UNITS/APT NUMBERS OR ALPHABETS | | | SHALL BE NO LESS THAN 3" IN HEIGHT IN | | | THE VICINITY OF THE FRONT ENTRANCE AREA. | | | | | | 4.) SMOKE ALARMS (DETECTORS) SHALL | | | RECEIVE THEIR OPERATING POWER FROM THE | | | BUILDING SERVICE ALONG WITH BATTERY | | | BACK-UP CAPABILITY. | | | | | | | | | PLEASE ADDRESS THE ABOVE IN YOUR | | | COMMENTS OR GENERAL NOTES. | | | | | | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|