2006-10-01 00:00:00*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW NOTES DUE TO REVISED PLANS
 SUBMITTED.
  
 1) NOTE: NO, PLEASE SEE DUE TO REVISED
 RISER, PELASE SEE SPECS NOW INDICATE A
 SE RATED ATS WHICH IS NOW NOT REQUIRED
 OF BEING FED FROM AN EXISTING METER MAIN
 WHICH CONTAINS OCP TO FEED THE PANEL
 "GP". PLEASE INDICATE THE OCP FROM TEH
 METER MAIN PANEL AND PLEASE SEE THE
 CONDUCTORS FROM THE METER MAINS AND TO
 THE PANEL "GP AND FROM GEN ARE UNCLEAR.
 SOME ARE MISSIGN AND THE OTHER
 CONDUCTORS WHICH SEEM TO BE SHOWN FROM
 GEN AND FROM ATS TO THE PANEL "GP" SEEM
 TO BE FUZZY FROM THE COPE?
 ** PLEASE CALL TO GO OVER WHAT IS NEEDED
 IF THAT MAY BE EASIER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARFIY THE USE OF THE
 SE RATED ATS AS THIS ATS CONTAINS A
 SERVICE ENTRANCE RATED MIN WHICH ONLY
 DISCONNECTS POWER ON THE LIN SIDE OF THE
 ATS.?
 PLEASE SEE THE EXISTING SERVICE CONTAIN
 THE REQUIRED "SERVICE ENTRANCE " RATED
 MAIN.
 A STANDARD ATS MAY BE USED AND A
 DISCONNECT IS REQUIRED FOR THE FEEDERS
 COMING FOMR THE GENERATOR GROUPED W/
 EXSITING MAINS OR THE PANEL GP CONTAINS
 A MCB.
 PLEASE CALL TO GO OVER POSSIBLE
 SCENERIOS.
 IFINSTALLING A DISCONNECT, THIS
 DISCONNECT DOES NOT NEED OCP, ONLY A
 DISCONNECTING MEANS.
 225.31-225.39, 230.72,230.2
  
 2) NOTE: NO, ?? PLEASE SEE COULD NOT
 LOCATE ANY INFORMATION WHETHER OR NOT
 THIS COUNDUIT IS FOR BRANCH CIRCUITS OR
 ???
 SIZE? ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE INFORMATION ON
 THE CONDUIT FROM PANEL "B"? IS THIS
 BRANCH CIRCUITS?
  
 3) NOTE: OK, LAYOUT PROVIDED, HOWEVER
 THE LARGER SET OF PLANS IS NOT NEEDED TO
 BE SUBMITTED.
 PLEASE BE SURE THART ALL PLANS SUBMITTED
 DO CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A LAYOUT OF ALL
 SERVICE EQUIPMENT AND LOCATION OVER VIEW
 , LIKE THE ONES SHOWN ON THE LARGE
 PLANS. AS ONLY THE INFORMATION FOR THE
 GEN NEEDS TO BE SUBMITTED. THIS CAN BE
 ON A 8 1/2 BY 11.
 106.1.2 FBC.
  
 4) NOTE: NO, FROM THE "SITE ALYOUT"
 SUBMITTED THE GEN DOES NOT INDICATE THE
 MINIMUM OF 3FT FROM STRUCTURE AND 5FT
 FOR EXHAUST FROM ANY OPENINGS.PLEASE SEE
 ZONING COMMENTS ALSO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, MIN CLEARENCE OF
 GEN FROM STRUCTURE OR WALL SHALL BE 3FT
 MIN BASED ON LTRS OBTAINED FROM
 MANUFCATURE. IF MIN CLEARNECES ARE LESS,
 PLEASE PROVIDE INFORMATION FROM
 MANUFCATURE. MUST BE ON THE SPECS OR
 FROM THE MANUFACTURE.
  
 ** SEE COMMENTS FROM OTHER TRADES.
  
 ** NEW NOTE **
 PLEASE SEE FS 553.80(2)(B) WHICH IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717