| 2006-07-21 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE CLARFIY THE USE OF TEH |
| | SE RATED ATS AS THIS ATS CONTAINS A |
| | SERVICE ENTRANCE RATED MIN WHICH ONLY |
| | DISCONNECTS POWER ON THE LIN SIDE OF THE |
| | ATS.? |
| | PLEASE SEE THE EXISTING SERVICE CONTAIN |
| | THE REQUIRED "SERVICE ENTRANCE " RATED |
| | MAIN. |
| | A STANDARD ATS MAY BE USED AND A |
| | DISCONNECT IS REQUIRED FOR THE FEEDERS |
| | COMING FOMR THE GENERATOR GROUPED W/ |
| | EXSITING MAINS OR THE PANEL GP CONTAINS |
| | A MCB. |
| | PLEASE CALL TO GO OVER POSSIBLE |
| | SCENERIOS. |
| | IFINSTALLING A DISCONNECT, THIS |
| | DISCONNECT DOES NOT NEED OCP, ONLY A |
| | DISCONNECTING MEANS. |
| | 225.31-225.39, 230.72,230.2 |
| | |
| | 2) NOTE: PLEASE PROVIDE INFORMATION ON |
| | THE CONDUIT FROM PANEL "B"? IS THIS |
| | BRNACH CIRCUITS? |
| | |
| | 3) NOTE: PLEASE PROVIDE A LAYOUT OF ALL |
| | SERVICE EQUIPMENT AND LOCATION OVER VIEW |
| | , LIKE THE ONES SHOWN ON THE LARGE |
| | PLANS. AS ONLY THE INFORMATION FOR THE |
| | GEN NEEDS TO BE SUBMITTED. THIS CAN BE |
| | ON A 8 1/2 BY 11. |
| | 106.1.2 FBC. |
| | |
| | 4) NOTE: PLEASE KNOW, MIN CLEARENCE OF |
| | GEN FROM STRUCTURE OR WALL SHALL BE 3FT |
| | MIN BASED ON LTRS OBTAINED FROM |
| | MANUFCATURE. IF MIN CLEARNECES ARE LESS, |
| | PLEASE PROVIDE INFORMATION FROM |
| | MANUFCATURE. MUST BE ON THE SPECS OR |
| | FROM THE MANUFACTURE. |
| | |
| | ** SEE COMMENTS FROM OTHER TRADES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |