| 2006-12-17 11:24:21 | *** UNSAT 3RD REVIEW*** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| | STILL NEEDS TO BE CLARIFIED OR ADDRESSED. |
| | THIS IS ACTUALLY THEFIRST SET OF PLANS BEING |
| | SUBMITTED FOR REVIEW UNDER THE THE NEW DESIGNER OF |
| | RECORD AS SHOWN. |
| | |
| | ** PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED PLANS |
| | FOR REVIEW FOR SCOPE OF WORK BEING PERFORMED. PLEASE |
| | SEE THE COMMENTS BELOW ARE BASED ON THE PLANS |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE PLANS MISSING CIRCUITING AS |
| | PREVIOUSLY REQUESTED. PLEASE SEE THAT THIS CIRCUITING |
| | SHALL CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| | 408.4, 310.16 |
| | |
| | 2) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED CIRCUITS |
| | FOR SMALL APPLIANCE CIRCUITS AND DINING ROOM CIRCUITS |
| | PER 210.52B1, 210.11C1, 220.16 |
| | |
| | 3) NOTE: PLEASE SEE EXISTING PANEL IS BEING SHOWN |
| | LOCATED SO THAT THE MINIMUM CLEARANCE IS NOT MET IN |
| | 110.26. PLEASE SEE NOTE ON PLANS MENTIONS THIS IS |
| | EXEMPT DUE TO INSPECTOR AND IS "GRANDFATHERED" PLEASE |
| | KNOW MINIMUM CLEARANCES IN THE CODE HAVE GONE BACK |
| | FURTHER THAN WHEN THIS BUILDING WAS CONSTRUCTED AND A |
| | LIFE SAFETY CODE HAZARD IS NOT "GRANDFATHERED" AS |
| | STATED ON PLANS. PLEASE KNOW THIS LICENSED PLANS |
| | EXAMINER WILL NOT MAKE ANY EXCEPTION TO THIS. PLEASE |
| | SEE 110.26, PLEASE RELOCATE AND MEET CODE OR PROVIDE |
| | DOCUMENTATION TO THE INSPECTOR WHICH WILL BE REQUIRED |
| | TO BE THE CHIEF ELECTRICAL INSPECTOR AND THE BUILDING |
| | OFFICIAL FOR ANY EXCEPTIONS. |
| | THIS REVIEWER WILL RELEASE PROJECT AT THAT TIME IF THIS |
| | EXCEPTION IS GRANTED AND NEW LICENSED PLANS EXAMINER/ |
| | INSPECTOR OR BUILDING OFFICAL WILL TAKE OVER REVIEWING |
| | AND SIGNING OFF OF CODE COMPLIANCE. |
| | |
| | 4) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI LOCATIONS |
| | AS REQUIRED PER 210.52C1 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTS TO BE LOCATED PER |
| | 210.52 |
| | |
| | 6) NOTE: PLEASE SEE THE SMOKE DEVICE IS BEING NOTED AS |
| | 110V W/ BATTERY BACK UP AND PLANS INDICATE UNIT AS A SD |
| | WHICH MEANS SMOKE DETECTOR. PLEASE SEE NFPA-72 |
| | DEFINITIONS AS A SMOKE DETECTOR IS IN FACT A DEVICE |
| | WHICH ONLY DETECTS AND IS PART OF A FIRE ALARM SYSTEM. |
| | IF THIS DEVICE IS INDEED A DEVICE WHICH DETECTS AND |
| | SOUNDS, THEN THIS DEVICE SHOULD BE SHOWN AND NOTED AS |
| | "SA" AS A SMOKE ALARM DEVICE. |
| | PLEASE KNOW THIS WAS PROVIDED TO THIS OFFICE FROM NFPA |
| | THAT NOTATION OF SD AND SA IS CLEARLY DIFFERENT AND |
| | SHALL BE INDICATED AS SUCH. |
| | |
| | 7) NOTE: PLEASE SEE ARC FAULT PROTECTION IS BEING SHOWN |
| | FOR RECEPTS ONLY WHERE THE 2002 NEC REQUIRES AFCI |
| | PROTECTION FOR ALL BRANCH CIRCUITING IN SLEEPING ROOMS. |
| | PLEASE LIST CIRCUITS ON PANEL SCHEDULE. |
| | PANEL SCHEDULE SHOWS AFCI FOR BATH ROOM? |
| | |
| | 8) NOTE: PLEASE SEE PLANS REFER TO A 2004 NEC. PLEASE |
| | KNOW AS THIS PROJECT CAME IN BEFORE THE CODE CHANGE |
| | THIS SHOULD BE SHOWN AS THE 2002. |
| | ** PLEASE KNOW THE NEXT CODE FOR THE NEC AFTER THE 2002 |
| | WILL BE THE 2005 NEC WHICH WAS ADOPTED ON 12/8/06. THIS |
| | PROJECT IS UNDER THE 2002. |
| | |
| | 9) NOTE: PLEASE SEE NOTICE OF COMMENCMENT STILL BEING |
| | SUBMITTED HAS EXPIRED AND HAS BECOME VOID . PLEASE SEE |
| | FLORIDA STATUTES 713.13(2). WHEN WORK HAS NOT COMMENCED |
| | WITHIN 90 DAYS OF RECORDING SUCH NOTICE OF |
| | COMMENCEMENT, THE NOC SHALL BEOMCE VOID. THIS WAS |
| | RECORDED IN JULY OF 06, A NEW RECORDED NOC WIL BE |
| | REQUIRED BEFORE PICKIGN UP PERMIT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |