| Plan Review Notes For Permit 06070698 |
| Permit Number |
06070698 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-02 00:00:00 | ***DENIED*** | | | | | | 1) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 3) PLEASE SHOW ALL EXISTING AND NEW EXIT | | | LIGHTS AND EMERGENCY LIGHTING EQUIPMENT. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED AT | | | DISTANCES NOT TO EXCEED 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|