| Plan Review Notes For Permit 06070696 |
| Permit Number |
06070696 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-19 00:00:00 | BUILDING REVIEW 2ND CHECKLIST; | | | | | | 1- SPECIFIC APPROVED ASSEMBLY TO BE | | | INSTALLED WAS NOT SELECTED AS REQUIRED | | | BY CITY POLICY FOR RE-ROOFING PERMITS. | | | SEE ATTACHED COPY OF CITY POLICY AND | | | PROVIDE ALL THE REQUIRED INFORMATION | | | | | | 2- FROM PREVIOUS CHECKLIST: | | | NOA 03-0130.08 LIMITATION #7 ALLOWS FOR | | | ENHANCED UPLIFT CALCULATIONS FOR | | | PERIMETER AND CORNER AREAS. SUCH | | | CALCULATIONS MUST BE DONE PER RAS 117 | | | ANDSIGNED AND SEALED BY ANY ONE OF THE | | | PROFESSIONALS LISTED IN LIMITATION #7. | | | SEE LIMITATION #7 AND PROVIDE THE | | | CALCULATIONS AS REQUIRED. | | | | | | ***NOTE: IF LIMITATION #9 APPLIES, THEN | | | SYSTEM CAN'T BE USED IN THIS AREA. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|