| 2008-04-14 14:59:04 | LETTER EMEMPT LOCATION TO FIRE SPRINKLERS, BUILDING | | | STIPULATION NO MERCHANDISE ON EXTERIOR OF BUILDING. | | | | | | 903.3.1.1.1 EXEMPT LOCATIONS. | | | | | | AUTOMATIC SPRINKLERS SHALL NOT BE REQUIRED IN THE | | | FOLLOWING ROOMS OR AREAS WHERE SUCH ROOMS OR AREAS ARE | | | PROTECTED WITH AN APPROVED AUTOMATIC FIRE DETECTION | | | SYSTEM IN ACCORDANCE WITH SECTION 907.2 THAT WILL | | | RESPOND TO VISIBLE OR INVISIBLE PARTICLES OF | | | COMBUSTION. SPRINKLERS SHALL NOT BE OMITTED FROM ANY | | | ROOM MERELY BECAUSE IT IS DAMP, OF | | | FIRE-RESISTANCE-RATED CONSTRUCTION OR CONTAINS | | | ELECTRICAL EQUIPMENT. | | | (4)IN ROOMS OR AREAS THAT ARE OF NONCOMBUSTIBLE | | | CONSTRUCTION WITH WHOLLY NONCOMBUSTIBLE CONTENTS. | | | | | | |
|