| 2007-07-10 11:56:19 | 2007-07-10 11:56:19 |
| | |
| | **** UNSAT 6THREVIEW **** |
| | |
| | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THERE ARE SOME ITEMS ON THE ENERGY |
| | CALCULATIONS WHICH DO NOT CORRELATE WITH PLANS. PLEASE |
| | KNOW THAT THIS IS THE FIRST REVIEW OF THE INPUT DATA |
| | REPORT AS IT WAS NOT SUBMITTED ON THE LAST REVIEW. THIS |
| | WAS NOTED ON PREVIOUS REVIEW. |
| | PLEASE BE SURE ALL AREAS WHICH ARE DESIGNATED ON PLANS |
| | ARE THAT OF THE SAME AREAS AS DESIGNATED ON THE ENERGY |
| | CALCULATIONS. PLEASE SEE SOME OF THESE AREAS ARE |
| | MISSING AND/OR DO NOT COORDINATE AT THIS TIME. PLEASE |
| | SEE IT IS NOT POSSIBLE FOR THE METHOD OF CONTROL FOR |
| | LIGHTING TO BE SHOWN AS *MANUAL ON/OFF* WHEN THE |
| | LIGHTING ON PLANS AND AS REQUIRED UNDER CHAPTER 13 OF |
| | THE FBC REQUIRES LIGHTING TO BE AUTOMATED. |
| | PLEASE SEE SOME SEPARATE SPACES STILL DO NOT INDICATE |
| | OVER RIDE DEVICES. PLEASE SEE 13-415.1.ABC1.2 AS THESE |
| | AREAS SHALL CONTAIN EITHER OF THE CONTROLS AS SET-FORTH |
| | HOWEVER MAY NOT ONLY CONTAIN A SINGLE POLE OR THREE-WAY |
| | SWITCH. THE DEVICE MUST BE CAPABLE OF OVER RIDING THE |
| | TIMED SCHEDULING WHEN ON THE TIMED SCHEDULE SYSTEM. IF |
| | AN AREA IS NOT ON THE SCHEDULED TIMER CONTROLS OR |
| | ENERGY MANAGEMENT SYSTEM THEM SEPARATE DEVICES SUCH AS |
| | OS TYPE DEVICES ARE PERMITTED. |
| | PLEASE SEE AREAS WHICH DO NOT CONTAIN OVER RIDE |
| | CONTROLS FOR EXAMPLE: PHARMACY, FAMILY TOILET ROOM (NO |
| | CONTROLS) , LIGHTING OUTSIDE OF TOILETS, ETC PLEASE SEE |
| | LIGHTS OUTSIDE OF THESE SAME ROOMS AND OTHER AREAS. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 2) NOTE: PLEASE SEE THE COVER SHEET C1 STILL INDICATES |
| | THE WRONG CODE FOR ELECTRICAL.. ALL OF THE PREVIOUS |
| | REVIEW STATED THE CODES WHICH NEEDED TO BE ON PLANS. |
| | PLEASE SEE THE PLANS STILL INDICATE THE 2002 |
| | NEC/NFPA-70. THIS SHOULD BE THE 2005 NEC/ NFPA-70. THIS |
| | CAN BE REDLINED. |
| | |
| | 3) NOTE: PLEASE KNOW THAT IT MAY BE POSSIBLE PENDING |
| | OTHER TRADE REVIEWS TO PROVIDE WHAT IS KNOWN AS A |
| | *PROVISO* FOR THE LIGHTING CONTROL PART OF THE COMMENT |
| | ABOVE AND COMMENT NUMBER 2. |
| | THE *PROVISO* WOULD SET-FORTH CONDITIONS THAT THE |
| | PERMIT CAN BE ISSUED AND THE LIGHTING CONTROLS ON PLANS |
| | WOULD NEED TO BE ADDRESSED AND SUBMIT REVISED |
| | ELECTRICAL PLANS WITHIN 30DAYS OF PERMIT ISSUANCE. |
| | PLEASE KNOW HOWEVER THAT THE ENERGY CALCULATIONS MAY |
| | NOT BE DONE AS A *PROVISO* AND MUST BE ADDRESSED AT |
| | THIS TIME. |
| | PLEASE BE SURE ANY REVISED ENERGY CALCULATIONS WILL BE |
| | REQUIRED TO CONTAIN ALL SIGNATURES FROM THE RESPONSIBLE |
| | PERSONS OF RECORD INCLUDING THAT OF THE OWNER AGENT. |
| | 13-103.1.1.1 |
| | *** IMPORTANT , THE REVIEW FROM THE MECHANICAL REVIEWER |
| | HAS NOT YET BEEN DONE FOR THE ENERGY CALCULATIONS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-09 20:06:07 | 2007-07-09 20:06:07 |
| | PLANS REMOVED FROM INCOMING FOR ELECTRICAL REVIEW. |
| | PLANS WILL BE RETURNED TO INCOMING WAITING FOR COMM |
| | BOARD ONCE ELECTRICAL REVIEW IS COMPLETED. |