| 2007-02-20 15:17:50 | |
| | ********** UNSAT 3RD REVIEW ************* |
| | |
| | ********** WAL-MART BUILD -OUT****** |
| | |
| | ** PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR "PLAN |
| | REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | |
| | 1 NOTE: PLEASE KNOW THAT IT IS MOST HELPFUL FOR A |
| | REVIEW IF A RESPONSE LETTER OF SOME TYPE IS SUBMITTED |
| | BY THE DESIGNER OF RECORD. PLEASE SEE THE RESPONSE |
| | LETTER CONTAINS TWO RESPONSES WHICH ARE BOTH LISTED AS |
| | ITEM #1 AND DO NOT INDICATE WHAT THEY ARE BEING |
| | RESPONDED TO?? |
| | |
| | 2) NOTE:PLEASE SEE THE PREVIOUS REVIEWS WHICH |
| | MENTIONED THE CODES REQUIRED DEPENDING ON WHEN PERMIT |
| | APPLICATION IS MADE. PLEASE SEE THE PLANS NOW LIST BOTH |
| | CODES FOR 2005 AND 2002 ARE BEING SHOWN ON PLANS FOR |
| | DESIGN ETC?? PLEASE MAKE THE CORRECTIONS. |
| | PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS |
| | #6 WILL BE REQUIRED. |
| | PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH |
| | SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED |
| | UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES |
| | ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS. |
| | |
| | 3) NOTE:PLEASE SEE THAT THE ENERGY CALCULATIONS |
| | SUBMITTED ARE STILL NOT SIGNED, DATED AND SEALED BY THE |
| | DESIGNER OF RECORD NOR ARE THEY UNDER THE CORRECT CODE. |
| | THEY ARE DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS |
| | NOT IN EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH |
| | PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1, |
| | 13-415.2 AND 13-103.1.1.1. |
| | REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT |
| | THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006 |
| | REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER |
| | 13. |
| | PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS, |
| | WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN |
| | COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE |
| | SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON |
| | OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME |
| | SCHEDULING ETC. |
| | PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH |
| | CHAPTER 13. |
| | |
| | PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13. |
| | PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR |
| | FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. |
| | PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM |
| | DETAILS. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES |
| | 415.2.C.1 AND 415.2.B.1. |
| | PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED, |
| | DATED AND SEALED BY THE DESIGNER(S) OF RECORD. |
| | |
| | 4) NOTE: THIS IS TAKEN FROM PREVIOUS REVIEW AS NO |
| | CHANGES TO ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE |
| | SEE THE MAIN ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND |
| | UNOBSTRUCTED PATH WHICH IT DOES NOT. THERE IS A WALL |
| | CLEARLY SHOWN WHICH WOULD IMPEDE THE EGRESS OUT OF THE |
| | ROOM IN AN EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS, |
| | AN ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND |
| | THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT |
| | ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR |
| | WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED |
| | TO CONTAIN PANIC HARDWARE. |
| | 110.26, 90.4 |
| | |
| | 5) NOTE: PLEASE SEE THAT THE PANEL LRX WHICH IS STILL |
| | BEING SHOWN IN A STORAGE ROOM. PLEASE RELOCATE. THIS IS |
| | A LIFE SAFETY AND PROPERTY SAFETY ISSUE AND WILL NOT BE |
| | PERMITTED IN THIS ROOM. |
| | PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY |
| | TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY |
| | IGNITABLE MATERIALS ETC. |
| | |
| | 6) NOTE: PLEASE SEE PLANS STILL FOR A KIRK KEY |
| | INTERLOCK WHICH DOES NOT PROVIDE A *FAIL SAFE* |
| | OPERATION. THIS OFFICE HAS REVIEWED DOCUMENTATION |
| | PROVIDED. THIS OFFICE HAS NOT MENTIONED THAT A LISTED |
| | TRANSFER SWITCH IS REQUIRED HOWEVER WE ARE REQUIRING |
| | THE DEVICE IS LISTED FOR USE AND THAT IT PROVIDES |
| | COMPLETE FAIL SAFE OPERATION. |
| | DEVICES AS SUBMITTED DO NOT PROVIDE THIS REQUIREMENT. |
| | PLEASE SEE 110.3, 90.7, 702.6 ETC. |
| | PLEASE SUBMIT ACTUAL SPEC/MANUFACTURES CUT SHEETS. |
| | |
| | 7) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR |
| | EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1, |
| | .2, AND .3(4). |
| | PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES |
| | AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION |
| | SHEETS WHICH ARE FROM TWO CODE CYCLES AGO. |
| | PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE |
| | 2002 NFPA-72 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-02-19 10:37:32 | 2007-02-19 10:37:32 |
| | REVIEW TO CONTINUE ON 2/20 NOTES TO FOLLOW , PLANS WILL |
| | BE PLACED INTO A "F" STATUS. |