| 2007-01-25 12:47:38 | ******UNSAT****** |
| | |
| | PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE |
| | PREVIOUS FIRE PLAN REVIEW (10/10/2006) WHICH HAVE NOT |
| | BEEN MARKED APPROVED.IN ADDITION SEE NEW COMMENT. |
| | |
| | |
| | |
| | 01.)NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED.(APPROVED) |
| | |
| | 02.)CONSTRUCTION, ALTERATION, AND DEMOLITION |
| | OPERATIONS SHALL COMPLY WITH NFPA 241. (APPROVED) |
| | |
| | 03)ON THE APPROPIATE EXTERIOR ELEVATION SHEET, |
| | SHOW/DISPALAY THE SUITE UNIT NUMBER OF THIS 6901 |
| | OKEECHOBEE BOULEVARD SHOPPING PLAZA.AS PER WEST PALM |
| | BEACH CODE, CHARACTERS ( NUMBERS AND/OR LETTERS) SHALL |
| | BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. |
| | (APPROVED) |
| | |
| | 04.)SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| | FOR FIRE SPRINKLER SYSTEM (APPROVED)AND FIRE ALARM |
| | SYSTEM.(SEE NEW COMMENT) |
| | |
| | 05.)FIRE SPRINKLER SHALL BE MAINTAINED OPERATIONAL |
| | UNTIL SUCH SUCH TIMETHAT THE SYSTEM IS DEMOLISHED. |
| | PRIOR TO THE SPRINKLER SYSTEM BEING TAKEN OUT OF |
| | SERVICE, NOTIFICATION AND APPROVAL SHALL BE ATTAINED |
| | FROM THE FIRE PREVENTION BUREAU.(APPROVED) |
| | |
| | 06.)DEMOLITION OPERATIONS INVOLVING THE USE OF |
| | CUTTING AND WELDING SHALL BE DONE IN ACCORDANCE WITH |
| | NFPA 51B.(APPROVED) |
| | |
| | 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND |
| | SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. (SEE |
| | NEW COMMENT) |
| | |
| | 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL |
| | FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. (SEE |
| | NEW COMMENT) |
| | |
| | 09.)LOCK-BOX ENTRY KEY SYSTEM WILL BE REQUIRED.SHOW |
| | THE LOCATION OF THIS DEVICE ON THE APPROPIAITE PLAN |
| | SHEET(S).(APPROVED) |
| | |
| | 10.)INTERIOR FINISH FOR WALLS AND CEILINGS SHALL BE |
| | CLASS "A" OR CLASS "B". |
| | |
| | 11.)ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 12.)PANIC HARDWARE TO BE INSTALLED ON EXIT DOORS WITH |
| | AN OCCUPANT LOAD OF ONE HUNDRED PERSONS OR MORE.IN |
| | RELATION TO POWERED DOORS, REFERENCE NFPA 101, 7.2.1.9 |
| | |
| | 13.)SHOW ON THE APPROPIATE FIRE PROTECTION PLAN |
| | SHEET(S) THE LOCATION OF THE 2A10BC RATED FIRE |
| | EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL |
| | DISTANCE REQUIREMENT.(APPROVED) |
| | |
| | NEW |
| | |
| | 14.CLASS A MERCANTILE OCCUPANCIES (GREATER THAN |
| | 30,000 SQ. FT.) SHALL BE PROVIDED WITH A FIRE ALARM |
| | SYSTEM.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED |
| | |
| | |